Print reading final

Ace your homework & exams now with Quizwiz!

Each tenant panel is to be fed with a ____________ SE cable.

#1 AWG Al

Other than low voltage signal systems, all wire shall be a minimum of ____________.

#12

The solid copper grounding jumper to be terminated on the telephone backboard should be __________ AWG.

#2

The Grounding Electrode Conductor run to the cold water pipe should be _________.

#2/0 AWG Cu

The Grounding Electrode Conductor run to the concrete enclosed electrode should be _________.

#4 AWG Cu

A storage battery supplying emergency lighting and power shall maintain not less than 87 1/2% of full voltage at total load for a period of at least _____ hour(s).

1 1/2

The feeder to panel D is to be installed in __________ EMT.

1"

Type F6 luminaires (light fixtures) are battery emergency lights per the Fixture Schedule. The batteries within these luminaires are required to maintain not less than 60% of the initial emergency illumination for a period of at least___________ hr.

1.5

The roof plan is drawn using _____________ scale.

1/16" = 1"

In aircraft hangars, lighting fixtures less than _____' above wings and engine enclosures shall be totally enclosed.

10

On circuits of 1000 V or less, overhead feeder spans up to 50' in length shall have copper conductors no smaller than No. ______.

10

When normal power is interrupted, the life safety branch must be connected to the alternate source of power and fully functional within ___________ sec.

10

Breakers used in panel PP-1 shall have a minimum interrupt rating of _____________ AIC.

10,000

The "future data center" has a junction box for future connection to ___________kW UPS.

100

The "generator room" is room number______________.

103

For open conductor spacing of outdoor feeders, conductors on poles, where not placed on racks or brackets, shall be separated by no less than _________".

12

If the GFCI receptacles shown in the bathroom (BATH) are located in the face of the cabinet, they shall not be located more than ____________″ below the top of the basin.

12

The dishwasher in each apartment is rated at ________W.

1500

The heater outlet is _________ W

1500

The square footage of the One Family Dwelling is _________________.

1540 square ft

In Class I, Division I locations, conduit seals shall be placed no farther than ____" from an explosionproof enclosure

18

The minimum depth of the underground conduit feeding the train depot is ______.

18"

If there are no cross lines on a conduit then it contains _____ conductors.

2

A 125 V, ____ A laundry branch circuit is required in dwelling units.

20

Each commercial building and occupancy with ground floor footage shall have at least one outside sign outlet rated at ______ A.

20

For general wiring in Class I, Division 1 locations, ________ may be used.

RMC

Per the NEC®, distribution panelboard EQDP2 is supplied by a(n) _____________ derived system when transfer switch ATS-EQ2 loses utility power.

Seperately

Minimum conduit size is ½" EMT and only ______________ connectors and couplings can be used.

Steel

The ampacity for copper and aluminum service entrance cable installed in the earth is located in ________ of the NEC®.

Table 310.15(b)(16)

All 15A and 20A, 125V receptacles installed in areas listed in 210.52, shall be listed __________ Receptacles.

Tamper resistant

Audible/visual fire alarm devices are to be mounted at 80"AF (or 6" below ceiling) whichever is less, to the center of the unit.

True

Locations where concentrations of combustible dust of an electrically conductive nature may be present in sufficient quantities to be hazardous are designated as Class II, Division 1.

True

Open squirrel-cage induction motors that have no sliding contacts may be used in Class I, Division 1 locations if they are identified for the location.

True

Panel LP3 is surface mounted.

True

Receptacles in Class II, Division I locations shall be part of the premises wiring.

True

Stranded wires 10 AWG and smaller may be connected to equipment by means of screws used with terminal plates having upturned lugs

True

The 1 ½" PVC conduit emerging from grade is required to continue horizontally underground for at least 36" and be sealed with 3" of duct seal where the control cable exits underground.

True

The 120 V, 15 A receptacle outlets in bedroom 1 (BR 1) are required to have AFCI protection.

True

The 120 V, 1φ, 15 A receptacle outlets in the dining room are required to have AFCI protection.

True

The F8 light fixtures are recess ceiling mounted.

True

The building is 19,140 square feet.

True

The disconnecting means for the mechanical unit is to be a NEMA 3R.

True

The grounding conductor in a cable assembly for cord-and-plug-connected equipment need not be insulated.

True

The insulation on the nine #14 AWG conductors running in the ¾" RMC from the junction box on the water tank leg to the junction box on the side of the water tank are required to have THWN insulation.

True

The interior of the 1½ rigid metal conduit (RMC) installed underground is considered a wet location.

True

The junction box mounted to the water tank leg is required to be 12" x 12" x 8" NEMA 7 enclosure.

True

The lay-in fixtures are to be fastened to the ceiling suspension system with fixture clips.

True

The lighting outlet shown in bedroom 2 (BR 2) is required by the NEC®.

True

The panel is located in the laundry area (LAU).

True

The receptacles in the laundry area (LAU) are required to be provided with GFCI protection.

True

The ¾ rigid metal conduit (RMC) indicated on the print meet the NEC® Article 344.30 support requirements.

True

The ¾ rigid metal conduit (RMC) installed on the exterior of the water tower is required to be listed.

True

Under some conditions, askarel-filled transformers may be used in Class II, Division 2 locations.

True

All 15 A and 20 A, 125 V and 250 V non-locking receptacles installed outdoors shall be a listed _____________-resistant type.

Weather

A well-ventilated room where flammable anesthetics are stored in approved containers shall be considered a ________________ area.

class 1 division 1

Locations where combustible fibers are stored are designated as _________.

class iii div 2

Where is the generator located?

concrete pad

Where is panel PP-2 located?

first floor main house

Rod and pipe type electrodes shall be made of _________ material.

galavanzed steel, stainless steel, copper-coated

Radiant floor heat is specified to be installed in the _________.

garage, workshop, studio garage, and basement

The Grounding and Bonding detail on sheet E7.0 is illustrating a(n) _________ system in accordance with NEC® requirements.

grounding electrode

The Electrical Circuitry Key detail states "(3) BRANCH CIRCUITS, GENERAL POWER AND LIGHTING CIRCUITS TO UTILIZE 3 HOT/NEUTRAL WITH COMMON GROUND." This type of wiring installation is referred to as a multi-wire branch circuit per the NEC®, and one way of providing a means to simultaneously disconnect all ungrounded conductors when using single-pole circuit breakers is to utilize __________.

handle ties

The feeder from transformer "T-EQ1" to panel "EQP1" consists of _________________.

4 #1/0, 1#6 grd

In motion picture studios, the ampacity of feeder conductors to the stage may be protected at a maximum value of _____%.

400

The electrical fixture allowance shall be $___________.

40000

In general, the requirements for the installation of on-site generators are located in section ______________of the NEC®.

445.1

In general, the maximum mounting height for switches for the project is ___________".

48

Switches should not be mounted higher than _______" to the center of the box above the finished floor

48

The oven in each apartment is rated at___________W.

4800

In operating rooms using flammable anesthetics, the entire area is a Class I, Division I location up to a level of _____' above the floor.

5

The receptacles installed in the bedroom of apartment A are connected to circuit number _________.

5

There is a quantity of __________ type "r" recessed light fixtures to be installed in the building.

5

Essential electrical system components are required to be located to minimize interruptions caused by natural forces such as storms, floods, earthquakes, or hazards created by adjoining structures or activities in accordance with NEC® Section ___________.Essential electrical system components are required to be located to minimize interruptions caused by natural forces such as storms, floods, earthquakes, or hazards created by adjoining structures or activities in accordance with NEC® Section ___________.

517.30

The electrical contractor shall install a security and alarm system not to exceed an allowance of $ _______.

5500

The size of the copper equipment grounding conductor run with the supply conductors to the detached garage is ____ AWG.

6

The primary voltage of an isolating transformer used in an anesthetizing location shall not exceed __________ V between conductors.

600

Circuit breakers or fuses installed in the Main Distribution Panel should be rated at least _______________ AIC.

65000

Fuses and circuit breakers installed in the "distribution switchboard" (MSB) must have a minimum ______________ interrupting rating.

65kA

The rating of a lampholder on a circuit operating at less than 50 V shall be at least _______ VA.

660

If the outlet box is the sole support for a ceiling fan, the outlet box shall be listed and shall not support ceiling fans that weigh more than _________ lb.

70

Transformer "T-1" is rated at ____________ kVA.

75

Ground rods are specified to be 10' long and shall be driven to a depth of not less than ____'.

8

The 2' x 4' Quazite box is to be installed flush with the finished grade, and on top of a layer of gravel ________" deep designed for drainage.

8

The pendant mount decorative light fixture under the covered entry above the front door is to be mounted at ___________" AFF to the bottom of the fixture.

8'-5 1/2"

The meter stack is 120/240V ______________ A.

800

The coaxial cable wiring and installation for systems that provide voice, data, video, and audio in residential applications shall comply with NEC® Article ______.

830

The television outlets in the conference room as well as the receptacle outlets supplying power to the televisions should be mounted at ___________"

84

____________ is the circuit number in Panel PP-4 for the kitchen range hood.

9

The ceiling grid in the wine cellar is __________ AFF.

9'-4"

The total connected kVA for PP-1 is __________.

95.10

Fire alarm pull stations must be installed within 72" of all exits.

False

Floor areas in minor repair garages without pits or below grade work areas shall be unclassified.

False

Hazardous concentrations of gas or vapor are not present under normal operating conditions in Class I, Division 1 locations.

False

NMS cable shall be permitted to be used in storage battery rooms.

False

Open outside areas within 20' horizontally from the fill pipe of an underground gasoline tank shall be considered as a Class I, Division 2 location to a height of 18".

False

Open spaces within 20' horizontally of a gas-dispensing pump are designated as Class I, Division 1 locations

False

Panel LP1 has a 225A main breaker.

False

RT3 is a 6 ton roof top unit.

False

The #2 bare copper ground conductor is required to be buried 24" deep.

False

The F2 light fixtures in the laundry area are night lights.

False

The junction box mounted on the side of the water tank is to be a NEMA 1 enclosure.

False

The light fixture in BR2 is controlled by a 3-way switch.

False

The water tower legs are not required to be bonded to the ground conductor

False

The ½ rigid metal conduit (RMC) installed on the exterior of the water tower is not acceptable for use as an equipment grounding conductor.

False

The "(_______)" notation on switches and outlets of the same circuit indicates which switches control the outlets.

O

The light fixture in the closet of the bedroom in apartment D is controlled by what type of switch?

Pull switch

The minimum number of small appliance branch circuit(s) required to serve all the wall and countertop receptacles in the kitchen (KIT.) is ______.

2

There are _________ outdoor receptacles

2

Rooftop unit number 1 (RT1) is supplied by______________ in a 1" conduit

3 #6 + 1 #10G

The attic access is 2ft-6in x _____________________.

3'-0'

An allowance of $________ shall be included in the bid for luminaires (light fixtures) for the second-floor apartment.

500

What is the power demand for the house water heater?

5kW

The "v" ceiling fixture in the entry of apartment a is fed from circuit number ________.

6

The feeder to panel B consists of 3 No. __________ THW.

6

______ style lighting fixtures are used in the grooming area.

F1

A 120 V, 1φ, 15 A outlet is required to be provided at each dwelling for the purpose of charging electric vehicles.

False

A single 15 A receptacle may be installed on an individual 20 A branch circuit.

False

Bedroom 3 (BR 3) in violation of the NEC® because the closet does not have a lighting outlet provided?

False

Heating cables in a concrete floor shall be placed on at least 2' centers from adjacent runs of cable.

False

The dining room contains 5 duplex receptacles.

False

The overcurrent protection device for a branch circuit supplying power to a 120 gal. fixed water heater can be rated less than 125 % of the unit's nameplate rating.

False

The receptacle outlet shown for the kitchen refrigerator (REF) is required to be provided with GFCI protection.

False

The receptacle outlets shown in the bathroom (BATH) are not required to be GFCI protected if they are not accessible.

False

The service is run overhead

False

The split-wired receptacle in the living room is controlled by a 3-way switch.

False

Connections depending solely on solder are not permissible as grounding equipment.

True

In accordance with the NEC®, the living area on the second floor is considered a(n) _______ unit and all NEC® requirements will be enforced for that type of occupancy.

dwelling

The detail for bollard lights states "ground fixture to circuit ground conductor." The proper NEC® term to be used is _______________ instead of "ground conductor."

equiptment grounding conductor

The requirement to orientate all duplex receptacles in the vertical position with the grounding slot at the top is located in electrical _______________.

general notes

The outdoor receptacles must be both _________________ and _______________.

gfci, wp

The main breaker as shown on the electrical single-line diagram on sheet E-6 is required by the NEC® to have _______________.

ground-fault protection of equiptment

The proper NEC® term for plugmold is_________ assembly.

multi-outlet

The GFCI outlets installed in the sides of the kitchen breakfast bar (BRFST BAR) must be located no more than _________″ below the countertop.

12

The hall bath contains ___________ GFCI protected receptacle outlets.

2

No parts of cord-connected luminaires or ceiling-suspended (paddle) fans in the master bath shall be located within a zone measured _______′ horizontally and ________′ vertically from the top of the bathtub rim.

3, 8

The electrical room contains a motor rated at _______ HP, single phase, 6.9A.

3/4

The service disconnect is to be a NEMA type ___________ fused disconnect switch.

3r

Bedroom 1 (BR1) contains _________ duplex receptacle outlets.

4

The minimum size outlet box for the project shall be ______________.

4" x 4" x 2 1/8"

The 120 V, 1φ, 20 A receptacle outlets in the living room (LR) are spaced such that no point on any wall is more than ________′ from a receptacle outlet.

6

Apartment A has an area of ____________ square feet.

709

Gray shading on the receptacle outlets indicates the receptacle is ________________.

AFCI protected

The weatherproof (WP) GFCI outlet shown in a damp location at the entry (ENTRY) is required to have a weatherproof enclosure whether or not the attachment plug cap is inserted.

False

Which room in the apartment has the split-wired receptacle outlet?

Living room

______________ cabled assemblies are permitted in the walls of the multifamily dwelling?

MC

The elevator (EL1) is fed from panel __________________.

MDP

The elevator pit lighting and receptacles are required to be supplied by a(n) _______ branch circuit.

Seperate

GFCI protection shall be provided for outlets that supply dishwashers installed in dwelling unit locations.

True

If the resistance of a single driven ground rod exceeds 25 Ω to ground, a supplemental electrode shall be added.

True

The center grip of the operating handle for the switch or CB when in the highest position shall not be more than 6' -7" from the floor or platform.

True

The service disconnect rating for a one-family dwelling shall be not less than ______A, single phase, 3-wire.

c.) 100

The unit lighting load for a dwelling unit, expressed in VA/sq ft, shall be_________ VA.

c.) 3

All 15 A and 20 A, 125 V and 250 V non-locking receptacles installed in a wet location are required to have a weatherproof enclosure whether the attachment plug is inserted or not. A listed outlet box hood that is identified as ___________-duty is to be installed for this purpose.

extra

Section ___________ of the NEC® may require additional receptacles for the servicing of the cooling towers.

210.63

Conference room 110 may be required to meet the minimum number of receptacle outlets as required by NEC® Section _________.

210.71

The two 4" schedule 40 PVC primary service conduits are required to have a minimum cover of _________"

24

The total connected load for phase A(L1) and B(L2) in PP-3 is 26.83 kVA. To find the total amperes, divide by ______ and provide a 125 A main breaker.

240

If transformer UT1 is owned by Memorial Hospital of Carbondale, the secondary conductors from the transformer to distribution switchboard MSB will be required to follow all the requirements of the NEC®, particularly Section ___________.

240.21(C)

The voltage rating and amperage rating of Panel PP-1 is __________.

240/120v, 400a

Per the NEC®, at least one 125 V, single phase, 15 A- or 20 A-rated receptacle outlet shall be in the same room or area of electrical service equipment and within _____' of the electrical service equipment.

25

NEC® Section ________ requires equipment grounding conductors of the wire type to be installed in each raceway when conductors in parallel are installed in multiple raceways.

250.122(F)(b)

There are two __________" PVC electric service conduits and two 2" telephone service conduits feeding the Veterinary Center that terminate on West 55th Street.

4

_______ duplex receptacle outlets are installed in the billiard room.

4

If transformer UT1 is covered by NEC® requirements, a supply-side bonding jumper would typically be required from the transformer to distribution switchboard MSB. If the conduit were non-metallic, then a supply-side bonding jumper of the wire type would be required. It is possible that an AHJ might require a 500 kcmil copper conductor to be installed in each of the eight conduits supplying MSB provided the conduits are non-metallic. The exception in the NEC® that could be used to argue that another means to bond the transformer enclosure on the secondary side could be used is _____________.

250.30(A)(2) exception

The automatic transfer switch for the generator is rated at __________ A.

260

One of the two GFCI receptacles shown in the hall bath must be located within _________′ of the outside edge of the basin.

3

The concrete slab is _________" thick

3

Panel PP-1, PP-3 and PP-4 are to be bonded to ____________ diameter ground rods.

3/4"

The east wall of the studio garage is _____' from the property stake on Western Avenue.

358.26

A #___________ AWG grounding electrode conductor is required to be run to the domestic metallic cold water service.

4

The size of the copper grounding electrode conductor required to connect to the concrete-encased steel reinforcing rods is ______AWG.

4

Lighting fixture "t" is a ______________ type lighting fixture.

Drum

A 70 A, four-pole transfer switch (ATS-EU) is supplied by feeder ID #40 from MSB and feeder ID #70 from the paralleling switchgear. The transfer switch is supplying a 15 kVA mini power center (ELT1) with feeder ID #40. Drawing _________ should be referenced when asking questions about the feeders and transfer switch.

E6.0

All light fixtures above whirlpool tubs and showers shall be ___________.

GFCI

The plans refer to wire sizes over 4/0 AWG as "MCM". This changed in the NEC® several years ago. The current edition of the NEC® expresses wire sizes above 4/0 A WG as __________.

Kcmil

Which room has the split-wired receptacles installed?

LR

Where can you obtain the template for the parking lot lighting base anchor bolt placement?

They are furnished with the pole

A 4AWG grounded conductor in a 277/480V system installed in a raceway, can be identified by a continuous white or gray finish

True

A conduit seal shall be required in each conduit run leaving a Class I, Division 2 location.

True

A location where cloth is woven is designated as Class III, Division 1.

True

The abbreviation "AFF" stands for _______________.

above finished floor

A(n) ________________ scale should be used for taking measurements on first and second floor garage/studio plan(GE1).

architect

The general rule with respect to the service disconnecting means states that a grounding connection sgall not be made to any ground circuit on the __________ side

b.) load

Where is panel PP-1 located?

basement main house

Ten 4" conduits are installed underground from the electrical vault to the paralleling switchgear in the Energy Center for future connection to existing hospital paralleling switchgear. Raceways shall _______________ where the conduits enter the paralleling switchgear.

be sealed

A receptacle outlet is required for a hallway that has a length of_______' or more.

d.) 10

For the kitchen small appliance load in dwellings, the NEC® requires ______ A circuit(s)

d.) two 20

Arc fault circuit interrupters are required in the _________.

dens, bedrooms, libraries

In general, a _________________ is required within sight of every electric sign on the project.

disconnect

Areas within 18" horizontally of gas-dispensing pumps are considered Class I, Division 2 locations to the top of the __________.

dispenser

A(n) ________________ scale should be used for taking measurements on the architectural site plan(T1)

engineering

The "grounding and bonding" detail requires 3 ground rods set 10'-0" apart in a triangle pattern connected using 4/0 bare copper wire. The connection to the rods must be by ___________ as prescribed in the detail.

exothermic welding

Where is the utility meter located?

exterior wall of main house

All 125 V, single phase, 15 A and 20 A receptacles installed in the locations specified below shall have GFCI protection for personnel except ________.

finished basements

All the panelboards are supplied from the main distribution panel (MDP), and the equipment grounding conductor is run with the feeder conductors. The neutral (grounded) conductor in the panelboard (load side) must be ______________.

isolated from the equipment grounding conductor and all non-currentcarrying metal parts

Mini power center ELP1 is serving loads for the ________________ branch.

lifesafety

The service is fed to the switchboard in the electrical room from the power company ______________.

manhole

An illustration with the note "HASH MARKS INDICATE #12 AWG CONDUCTORS ONLY SEE FLOOR PLANS FOR OTHER FEEDER CONDUCTORS AND CONDUIT SIZES" is shown in the wiring symbols on sheet E1.0. This illustration indicates a _________ branch circuit per the NEC®.

multiwire

The electric service and meter are located on the ___________ side of the main house.

north

Per the NEC®, the locator tape as shown in the Ductbank Details on sheet E2.0 is to be _______.

not required

The watts per square foot when calculating the general lighting load for the studio garage is _______.

not specified

The Energy Center does not contain any ______________ spaces.

patient care

The "A" lighting fixtures in the mechanical room are _________________ mount.

pendant

All closet lights shall be switched using a ______________________.

plunger switch

The serving utility company generally specifies the service ___________, which is where the connection between the facilities of the serving utility and premises wiring is located.

point

For safe and ready access for persons entering manholes for installation and maintenance, the conductors shall be cabled or ____________ in accordance with NEC® requirements.

racked up

Exposed conduit below 48"AF shall be ________________ conduit.

rmc

The conductors from the existing utility pole to MSB-A-5KV are provided and terminated by _____________.

the utility company

The F1 light fixture uses _______________ lamps.

three 32 Watt

All exterior site lighting, yard lighting, garage exterior lighting, and house exterior lighting is operated by a _______.

time switch

Where is panel PP-5 located?

train depot

Where is panel PP-3 located?

two-car garage

Effectively isolated storerooms and similar areas adjacent to aircraft hangars shall be designated as ________ where adequately ventilated.

unclassified

Where is the transformer located?

utility pole


Related study sets

Pediatric success, Saunders & Davis test 2 questions

View Set

Nutrition - Chapter 2 (Planning a Healthy Diet)

View Set

Business Law II Chapter 32 Practice Questions

View Set

Biology chapter questions 22,23,24,25,26,29,30

View Set

Personal Finance Ch 3 Money Management Strategy: Financial Statements and Budgeting

View Set

A.P. Psychology Unit 3 Review (Parts A and B)

View Set

Biology Midterm Packet Questions

View Set