PT 2 LT ONLY/FIRE TECH

Ace your homework & exams now with Quizwiz!

ROWFRAMES A: They are built in rows containing as many as TWENTY OR MORE BUILDINGS B:They vary in height from 3-5 STORIES C: They are 20-30 FT IN WIDTH D: They have 40-60 FT DEPTH They were constructed over a period of many years in the 1800's and early 1900's. BS/RF 5.1.1

"Potential blast zone" established at a major gas emergency: 1) Subsurface leak; 2) 80% of LEL or higher (leak found); 3) gas leaking for considerable time and trapped in a voids space; 4) 10% LEL or greater (leak cannot be found); 5) 10% LEL or greater and there are indications the leak is coming from an outside DON'T CONFUSE SUBSURFACE LEAKS...TWO SUBSURFACE LEAKS ELEVATES IT TO A MAJOR GAS EMERGENCY, BUT AT A MAJOR EMERGENCY A SUBSURFACE LEAK REQUIRES A POTENTIAL BLAST ZONE AT A MAJOR GAS LEAK, A SUBSURFACE LEAK'S POTENTIAL BLAST ZONE IS MARKED WITH DANGER DO NOT ENTER TAPE CROSS REF AUC 362: MEMBERS CAN ONLY PASS BEYOND DANGER DO NOT ENTER TAPE FOR "SIL": SECTOR CHIEF APPROVAL IC APPROVAL LIFE Natural Gas 8.0 Pg 30 & 31

Operations mandates that TRAINING ROLL CALLS be conducted to keep members well versed in emergency roll call procedures. Quarterly (January, April, July, October) Whenever the incident commander feels it's warranted.

"Security of Quarters," A: Doors and windows that are easily accessible from the street, yard, court or adjoining roof should be kept locked when not in use B: If there is a contractor in quarters, and the doors and windows can be locked or secured, the officer on duty shall notify the contractor that the contractor will be held accountable while his personnel are working in quarters during the absence of the unit C: When the company is leaving quarters, entrance and apparatus doors are to be closed and locked by THE ASSIGNED MEMBER D: To gain access to another unit's quarters upon relocation that has a combination lock, the officer shall look at the response ticket for the combination. In case of no response ticket, the officer shall contact the dispatcher by the use of a nearby ERS Box AUC 300 sec 2

At a recent cellar fire in a 3-story row frame: A: The first hoseline was stretched through the front door and members then attempted to make it down to the cellar via the interior stairs to extinguish the fire. B: Since the first hoseline could not be advanced down to the cellar due to the intensity of the fire, it remained in position to protect the public hall, interior stairs, and the first floor. C: Since the first hoseline was covering the first floor public hall and did not need a back up line, the second hoseline was stretched into the cellar via the outside cellar entrance to extinguish the fire. Note: The second hoseline shall back up the first hoseline. If the first hoseline has advanced into the cellar, and a back up line is not needed, the second hoseline shall extinguish any fire on the first floor then proceed to the top floor. If the first hoseline is used to cover the first floor public hall, and a back up line is not needed, the second hoseline will be stretched into the cellar via the outside cellar entrance to extinguish the fire D: The first hoseline advanced to the TOP FLOOR to cover extension to that area and the cockloft after the cellar fire was controlled by the second hoseline. Note: Intervening floors shall be checked for fire on the way to the top floor. A member must be stationed on the landing to warn of any fire that may break out below them

**In what way do wood braced-frame constructed buildings collapse? Inward/Outward Collapse: The collapse of an exterior wall that breaks apart horizontally; the top collapses inward back on top of the structure and the bottom collapses outward on to the street. Wood braced-frame constructed buildings collapse this way. Timber truss roof collapse can cause a secondary collapse of a front wall in this manner Collapse Add 3 2

All members of the Department should be familiar with terms in the realm of Fire Dynamics: A: FLASH POINT is the lowest temperature of a LIQUID at which that liquid gives off sufficient vapors to ignite but WILL NOT continue to burn. In other words, at the Flash Point, the vapors will "flash"/blow but not sustain burning. While at the Fire Point, the vapor will continue to burn after the initial ignition B: FIRE POINT is the lowest temperature at which a LIQUID will ignite and achieve sustained burning. C: VAPOR PRESSURE is the ability of a LIQUID or SOLID fuel to VAPORIZE. The higher the vapor pressure, the more vapors are released (the easier it is to off-gas). D: The "Vapor Density" of gas refers to its density compared to air. A gas with a vapor density greater than 1 is heavier than air while vapor densities less than 1 are lighter than air. Note: Gases that have a vapor density around 1 will mix evenly with air. TB FD 6

A Carbon Monoxide (CO) investigation will determine if the response is an "Incident" or an "Emergency." A: SCBA WORN at all CO Incidents and USED at Emergencies B:If meter readings of 9 PPM are detected, inform occupant our meter has NOT detected an elevated CO level C: Members shall start mandatory evacuation of occupants if meter readings are 100 PPM AND GREATER D: A CO "Incident" is when meter readings are 9 PPM or less and/or an occupant is NOT considered symptomatic Emergency Haz-Mat 4 sec 4

After your unit was involved in a minor collision, you would be correct to a. Ensure the collision report is submitted within 48 HOURS of the collision. b. Upload the police report to the CRS App. DO NOT EMAIL THE POLICE REPORT or MV-104 c. Ensure the form MV-104, if required, is completed and sent to the NYS DMV within 10 days. The EXPRESS RESPONSIBILITY OF THE OPERATOR d. Forward a completed MV-104, through the bag, to the mailroom so it can be stamped and mailed. (SB 3 11.1, 11.2.1, 14.2)

A lieutenant drilling with the members of his ladder company on elevator operations: a. The 1620 key is not removable from the elevator car keyed switch when it is in the Fireman Service position. b. When recalled, an elevator traveling away from the street floor or from its lowest landing floor will reverse direction at the next landing WITHOUT opening its door,, then return non-stop to the lobby or terminal floor after its door closes. c. The "Emergency Stop" button is rendered inoperative in Phase 1 AND SHOULD WORK IN PHASE 2 d. Once a Fire Service car has been placed in Phase 2 recall operation (OPERATIONAL PHASE, WE'RE USING IT), it will continue in Phase 2 operation regardless of the position of the lobby keyed switch

The chain saw is a very dangerous tool that must be operated with proper care: A: Never make plunge cuts with the tip of the blade. B: Never use the tip of the blade for cutting. C: Never overreach to operate the saw above your SHOULDERS D: EXCEPT FOR PIER FIRE OPERATIONS, the chain saw IS NOT TO BE USED for the ventilation or overhauling of structural fire (CAN BE USED IN COLLAPSE) TB Tools 24: 2.1,5.6, 7.7

AERIAL OPS Since the aerial ladder was committed to the roof, and was the only safe egress from the roof, it was not moved unless absolutely necessary. Note: If it must be moved, direct radio communication must be made with members on the roof. It must also be evident that there is no immediate need for roof egress at the time and that this new critical task will not delay the prompt replacement of the aerial ladder at the original location. Units shall be informed of this temporary removal and the ladder must be returned to the same location as quickly as possible.

A Battalion Chief visiting your unit for company drill on Stack Effect: a. LATERAL AIR MOVEMENT will be strongest at openings (windows) or locations on the uppermost and bottommost floors. NOT VERTICAL! b. Of all the conditions that can affect fire behavior, WIND has the most dramatic impact. WINTER, WARMER INSIDE, POITIVE STACK EFFECT SUMMER, REVERSE STACK EFFECT

Activation of the Emergency Alert Button on the Handie-talkie will cause: a. The high visibility LED Light blinks out SOS signal (3 Dots, 3 Dashes, 3 Dots) b. The Transmit/ Receive light on the top of the remote speaker microphone blinks RED c. The main screen displays "Emergency" in a ORANGE STRIPE d. The top display will illuminate in Orange/ Amber and alternate between "Emergency" and "Unit ID". (Communications 11 3.5.1)

While conducting a drill on solar panels you made several statements. A: Firefighters must never cut any wires associated with the solar panels B: Firefighters must avoid walking on solar panels since this can expose them to electric shock C: Shutting off power at the main electric panel DOES NOT ensure that all power to the building has been removed D: The only way to ensure electricity does not enter the building from the solar panels, batteries, or back-up generator is shutting the switch to the iNVERTER AUC 351 sec 6

Aerial ladder unit tactic: A: In order to facilitate an efficient, coordinated operation, the officer of the first ladder company should strive to enter the block after the first engine company, and from the same direction. This is particularly important where street width or parked cars would prevent the engine from passing the ladder apparatus to reach the desired hydrant. B: If the second ladder company to arrive is moving into the fire block opposite the first engine company, the ladder company officer must VERIFY THAT THE ENGINE HAS A HYDRANT before moving too close. The officer and non-committed members (excludes chauffeur or tiller firefighter) may approach the fire building on foot C: When approaching a box location and there is no visible indication of fire on the avenue of approach, the chauffeur should slow down one intersection short of the box location and enter the intersection at a SLOW RATE OF SPEED. This will allow the members to look in the side streets for the fire or emergency D: At vacant building fires, officers of aerial ladders shall consider the need for access and positioning of tower ladders; however, precedence may be give to the positioning of aerial apparatus if the building is not completely vacant, there is information/prior knowledge of vagrants/squatters or the reach of the 100' aerial is required. Lad 2 6.3, 6.3.1 D, E, 6.6.1, 7.2.1

All firefighters should have a basic understanding of the various types of combustion: A: Flash fires involve a flame moving though a flammable mixture with considerable speed, without developing a significant over-pressure. B: Flash fires USUALLY self-extinguish, although SOMETIMES may ignite secondary fires C: Flash fires which occur in a CONFINED SPACE can cause an over pressure condition and result in an explosion. This condition would be referred to as an explosion. (e.g. dust explosion) D: A BLEVE occurs when liquid in a pressurized vessel is at or heated to a temperature that exceeds it boiling point and the container ruptures due to excessive buildup in pressure to tank failure caused by mechanical or thermal damage. TB FD Ch 3 8.1, 8.3, 8.4 Note, 9.3

At a recent top floor fire in an Old Law Tenement, which member/team of the 2nd arriving Ladder Company operated: A: The Inside Team proceed to the top floor to assist the 1st arriving Ladder Company in entry and search of all top floor apartments. B: The Roof FF proceeded to the roof with the power saw. C: The OV FF vented the FIRE APT from the fire escape. D: Chauffeur Position - Front of fire building. If not needed here, proceeds to the ROOF. Lad 3 3.5.2

Portable ladder markings: A: The numerical length of a straight ladder shall be marked on the side of each end rail within 12 inches of the end of the ladder. B: The numerical length of an extension ladder shall be marked on the side of the rails within 12 inches of the butt end only of the bed ladder. C: The unit designation shall be marked within 18 inches of each "butt" whether it is a straight ladder or extension ladder WRONG ANSWER WAS: The unit designation of a straight ladders shall be marked within 18 inches of each end of the ladder. D:The unit designation of an extension ladder shall be marked within 18 inches of each butt of the ladder. "6.2 The unit designation shall be marked within 18 inches of each butt." Note: Ladder length markings shall be visible when ladders are stored on the apparatus. Lad 1 6

All members assigned to a Tower Ladder should be proficient in "bucket" operations: A: Whenever a Tower Ladder operation is in progress, the pedestal position should be staffed. This provides an extra pair of eyes to warn of impending danger and override bucket controls in an emergency. B: Each member operating in a Tower Ladder bucket must personally verify the placement of both door latches. C: Each member operating in a Tower Ladder bucket must ensure proper use of the installed safety belt or life belt/personal harness secured to a substantial part of the bucket (one of the BUCKET POSTS OR THE WATERWAY) prior to raising the boom from the bedded position. D: Prior to gaining entry by way of the bucket, members should clear the entire window. Setting the end of a 6' hook firmly into the CORNER of a WINDOW SILL, and/or placing the bucket cord light into the window to be entered, may offer a reference point in the event a hasty retreat is required. TL Ch 3 3

Ladder company 300 just returned to quarters from a 2nd alarm fire in a project building. Members were faced with a punishing fire in a large storage room in the basement. The only entry to this area required the irons firefighter to force a door locked by a multi-lock: A: MULTI-LOCK is NOT NECC CENTERED INTO THE DOOR but is easily recognizable by the large plate covering the lock. NOTE: THE DOUBLE BAR LOCK-FOX LOCK IS EASILY RECOGNIZABLE BY THE LOCATION OF THE CYLINDER IN THE CENTER OF THE DOOR B: FOUR BARS, one in each direction, enter the DOOR JAMB when the lock is engaged. C: Prior to forcing entry, make sure the lock is engaged by sliding paper or cardboard under the door along the bottom. D: To force the door, cut a triangle in the lower quadrant of the door ON THE DOORKNOB SIDE TB Forcible Entry 1 9.1

All members should be familiar with the process for engaging the Engine apparatus pump in order to supply a hoseline: A: 1. Place the apparatus transmission in "neutral". B: 2. Engage the apparatus maxi-brake. C: 3. Move the "pump shift CONTROL" to the PUMP POSITON (located in the cab). D:4. Place the apparatus transmission in "DRIVE". Eng Ch 2 Add 1 3.1.1 LADDER PTO 1 NEUTRAL 2 MAXI-BREAK 3 FRONT BREAK LOCK SWITCH TO ON POSITION 4 RED COVERED PTO SWITCH UP POSITION

Units operating at a sub-cellar fire in a cast-iron loft building: a. CAST-IRON LOFT BUILDINGS buildings typically only have ONE INTERIOR STAIR c. If the 1st hoseline is stretched to the fire area by way of an exterior entrance, the 2nd line should be stretched to the 1st floor to protect the public hallway and interior stairs d. Initial hoselines may be 1 ¾", however, any fire in a large, uncompartmented area will require 2 ½" hose CROSS REF: For fire operations in non-residential fireproof loft buildings, initial hoselines shall be 2 1/2 inch.

An engine officer ordered by the Incident Commander to apply water on an energized solar panel (PV) fire would be most correct to apply water using: A fog stream, utilized from a distance, set at a 30-degree angle spray pattern NOTE: NOT 30 DEGREE OR GREATER (AUC 351 6.4)

Hydra Ram The ram requires no replenishment of fluids. The ram does not use hydraulic fluid. After fully extending the working piston, the operating arm should not be able to move except for when the relief valve is depressed. The entire tool can be cleaned with soap and water, including the pistons. Do not use spray type lubricants such as WD40 as they can damage the rubber seals. (TB Tolls 26 5)

At a recent All-Hands fire, the EMS Supervisor on scene informed the IC of the following patient count; 2 Green Tag civilians, 2 Green Tag firefighters, 1 Yellow Tag civilian, 1 Yellow Tag firefighter, 1 Red Tag civilian, 1 Black Tag Civilian. The IC would be correct to inform the dispatcher of which of the following 10-45 codes: One Code 1, One Code 2, One Code 3, Two Code 4 *FIREFIGHTERS DO NOT COUNT AS 10-45s

FIRE DYNAMICS FLAMMABLE LIQUID is a liquid that has a flash point BELOW 100'F COMBUSTIBLE LIQUID is a liquid that has a flash point EQUAL OR GREATER than 100'F.

At a structural collapse operation, certain tools are required to be used under specific conditions: A: Jackhammers, concrete cutting saws and torches are required for Class 1 buildings. B: CHAINSAWS ARE APPROPRIATE at most buildings with wooden floors and roofs. C: HEAVY DEMOLITION EQIUP (cranes, bulldozers, etc.) ARE FORBIDDEN during the SELECTED DEBRIS REMOVAL STAGE D: Tools that produce no exhaust fumes, such as battery or electrically powered tools, are preferable to gasoline driven units. Note: Besides emitting no fumes, electric tools are easier to put down and pick up again without the hassle of having to shut them off and restart them; moreover, they lack the noise of a gas engine. Collapse 11.13.2, 11.13.4

AERIAL LADDER SAFETY A: Avoid moving the ladder while members are on it, except to remove them from serious exposure or for an extreme rescue effort. B: Do not extend or retract the ladder while members are on it. C: Avoid extending the tip of the ladder against a structure. This INCLUDES pushing or lifting cornices and trying to open sealed windows in vacant buildings D: Never move the truck with the ladder raised to one side. Retract the sections substantially and turn the ladder parallel to its bed. Lad 2 8.9, 8.10, 8.14, 8.21

Auxiliary Radio Communications System: A: To activate a building ARCS, insert a 1620 key into the dedicated receiver console and rotate the key one position CLOCKWISE B:When choosing the primary HT building repeater channel, Choose the primary HT building repeater channel - Channel 11 - NOT CHANNEL 12 C: If both channels are needed, to activate a second repeater channel, a SECOND 1620 key will be REQUIRED. D: When you insert your 1620 key into the ARCS console, the key is NOT removeable in the ON/Active position. COMMUNICATIONS MANUAL - CHAPTER 13 - ARCS

When operating at a gas emergency, which of the following letters stamped on a tag near the service meter indicates there is no curb valve or service valve? "NC"

BARS ALARM response was received; Only the first due engine responded in emergency mode.

Oxygen in the air is the primary oxidizing agent in most fires: A: Normally, air consists of 20.8% oxygen. B: At normal ambient temperatures, materials can ignite and burn at oxygen concentrations as low as 15%. C: When oxygen concentration is reduced below 15%, the FLAMING combustion will DIMINISH, causing combustion to CONTINUE in the NON-FLAMING This means that below 15% there will not be visible flames, but because combustion continues in the nonflaming mode, heat and dense, fuel rich smoke will continue to be produced. If oxygen is introduced to this type of atmosphere, the fuel rich environment can ignite and be hazardous to firefighters D: When oxygen concentration is higher than 20.8%, materials exhibit very different burning characteristics and materials that burn at normal oxygen levels will burn more intensely. TB FD 2.6.1-2.6.3

BRUSH FIRES SURFACE FIRES are the most common type of brush fire encountered in NYC Units are not to self-commit to operations unless structures are exposed

When operating at wires down in the street units shall stretch a line with a fog nozzle and use distance as a safety factor keeping at least how many feet away from any downed wire while operating this handline: 25 TB Emergencies 3 8.2

Base Station Leaky Cable Simplex UHF or VHF Radio System: A: It is simplex radio that can operate on FDNY UHF HT channels 1-8 B: Transmissions captured by the cable Are not automatically re-transmitted C: Important messages that need to be heard by all members should be retransmitted at the base station radio by the member monitoring transmissions. D: Base Station Leaky Cable Simplex UHF or VHF Radio Systems are operated by a 1620 KEY COMMUNICATIONS MANUAL - CHAPTER 13

At a recent operation with heavy fire on the 4th floor of a 5-story rowframe, and extending into exposure 2, arriving Engine companies stretched a number of handlines: A: The first hoseline was stretched to the location of the fire via the interior stairs. It had sufficient lengths to cover the entire building. B: The second hoseline backed up the first hoseline on the fire floor. This hoseline had sufficient length to cover the entire building. Note: The SECOND HANDLINE, if not needed to back up the first hoseline, should be stretched to the top floor or to the floor above. If fire is reported in the exposure, the second hoseline MAY be more effective being stretched to the exposure, with the third or fourth hoseline stretched to back up the first hoseline. This hoseline will need to have sufficient length to cover the entire building C: The THIRD HOSELINE was stretched through an exposure to the rear yard, as ordered by the IC. THIRD HOSELINE IS FEX-TEX D:One of the 2nd ALARM Engine companies was ordered to stretch a hoseline to the top floor of exposure 2 to extinguish fire in the cockloft; An engine company, ordered to stretch a hoseline to the top floor of an exposure for purposes of extinguishing the fire in the cockloft, should take a SIX-FOOT HOOK to pull ceilings. BS/RF 6.1 C, 6.4

CIVIL DISORDER A: Members are to avoid personal engagement or confrontation with civilians. Where doubt exists, as to the ability of the FDNY to proceed safely, members should wait for NYPD force protection and support B: **The Task Force convoy consists: 1 BC, 2 Engines, 1 Ladder, and EMS. In the event of an apparatus breakdown, the Task Force convoy should remain intact until assistance arrives C: All warning lights are to be "on" for daytime as well as nighttime D: Air horns are not to be used during Task Force response unless directed by Task Force Force Leader E: Task Force preliminary reports via radio shall be Limited to coded radio signals NO PLAIN SPEAK CROSS REF: TACU, DO NOT USE CODED FD SIGNALS Explanation:Limited to coded radio signalsERP add 3B sec 3.5, 4.4.7, 4.4.9, 4.4.10, 4.8.1

Exterior walls can be breached with a maul and/or power tools for life saving or stream penetration: A: When using the MAUL to breach cinder blocks, START AT THE TOP. Note: In many instances blocks are filled with concrete to provide an added layer of strength and starting at the TOP will provide quick access as this area is usually HOLLOW B: When the power saw is being used to cut through brick and concrete, the combination metal/concrete saw blade (diamond blade) shall be used. C:Cuts in brick walls should be triangular with the vertex angle UPWARD to prevent further collapse. D: The first and second cuts should be at the brickwork since the easiest cut is at the mortar joint and the blade at this point will usually be worn. TL Ch 5 5.2

CO When using a CO meter, take an initial reading at the front door of premises, then continue investigation to find source of CO in premises A CO "Incident" is when no occupants are symptomatic and meter readings are 9 PPM or less

COMMS 6 Between the hours of 0800 & 2300 if there is no contact with the caller on an ERS box, there is NO RESPONSE

CO METER The Drager CO meter activates an alarm when the atmosphere is 35 PPM of CO or greater (slow modulating tone) and again when the atmosphere is at 100 PPM of CO or greater (fast modulating tone)

Units are operating at a gasoline spill for an overturned vehicle. The Lieutenant in the Engine orders his members to stretch a foam handline. After the officer calls for water, the ECC should start water providing what pressure at the eductor? 200 Explanation:TB Foam Evolution 1 2.4

CON ED FACILITIES AUC 338 Fog Streams can be greatly affected by wind conditions and may not reach the target area from a distance of 15-25 feet In these situations a straight stream utilizing the fog tip or a solid stream shall be used with standoff distances Exposed electrical Bus - 3'' Aluminum Bars 345,000v Safe Distance is 18 Feet 15,000 - 38,000v Safe distance is 10 feet AL/TL 18 FOOT SAFE CLEARANCE HORIZONTALLY from the substations exterior fence line BATTERY ROOMS - TYPICALLY 2 as many as 60 Car-type Batteries.WARNING SIGN. on locked door SULGURIC ACID- Led acid batts 5-10 gallons of 30-40% Acid

At a 2nd alarm structural fire, who is considered the Water Resource Officer if the delivery of water is a problem? Satellite officer Prior to a 2nd alarm the Water Resource Officer is the 2nd arriving engine officer....Engine Operations ch 4 sec 11.2* The 2nd eng off is the water resource officer UNTIL THE SATTELITE ARRIVES At a 2nd alarm (that's when a Satellite Unit is assigned to structural fires) the Water Resource Officer is the Satellite Unit Officer (1st arriving Satellite Unit).... AUC 274 sec 1.2.4 and Comm ch 7 p-23

Climbing the aerial ladder with tools: A: HAND RAILS are generally used when climbing the ladder with a tool. B: At STEEP ANGLES, greater safety is achieved by using the RUNGS when climbing the ladder with a tool. C: The 6' hook need not be carried on the ladder. The hook is extended arm's length overhead and hooked on a rung. D:When on a rung, the hook is not touched again until the member has climbed to a position where the top of the hook is about KNEE LEVEL Lad 2 7.15

Of the following choices, which is indicative of a new law tenement (built on or after 4/12/1901 and before 1916) A: Generally six or seven stories high, 35' to 50' wide and 85' in depth. B: The first floor (cellar ceiling) is of fireproof construction and unpierced. The entrance to the cellar is by way of exterior stairs. C: The interior stairs are fireproof and enclosed in partitions of fireproof construction. Apartment doors are constructed of fire-resistant materials. D: The second means of egress is either another stairway or an exterior fire escape. The FIRE ESCAPE is more generally found in these buildings. Notes: Five to six apartments per floor. All interior walls and furred partitions are required to be fire stopped at each story. Steel "I" beams were introduced to carry floor joists which couldn't span the enlarged floor areas. These steel beams generally were supported by masonry walls. MD Ch 1 1.2

ENGINE OPS At least 1 full length of hose is needed to cover the fire area. Larger apartments or fire areas MAY require 1 ½ LENGTHS.

TAC U channel has been programmed to allow for FD/PD interagency communications: A: Zone "B" channel 12 is designated as the TAC "U" Channel. This channel transmits at 5 watts. B: When the TAC U channel is activated, all operating units shall remain on the Primary tactical channel unless specifically instructed to switch to another channel. C: If an EMERGENCY ALERT TONE is activated, only members of the FDNY will receive the alert over their HT's and only on the channel on which the EA was activated. D: Users of Interoperable (I/O) frequencies are reminded to use plain language and refrain from using 10 codes or FD terminology while communicating on these frequencies. CROSS REF: ERP 3B CIVIL UNREST Task Force preliminary reports via radio shall be Limited to coded radio signals NO PLAIN SPEAK COMMUNiCATIONS MANUAL - CHAPTER 14 - ADDENDUM 2

Con-Ed Substation: A 3 1/2" supply line shall be stretched, but not charged to the sprinkler Siamese if present. if requested by Con-Ed white hat, supply the Siamese with water at the posted pressure. Sprinklers if present PROTECT ONLY THE TRANSFORMERS B: Carbon dioxide extinguishers should not be used as an extinguishing agent at battery room fires USE DRY CHEM C: When raising Al or TL maintain an 18 foot safe clearance horizontally from the substation's exterior fence line D: Ask the Con-Ed White hat to retrieve the information from the FDNY lockbox located INSIDE THE SUBSTATION AUC 338 add 2

When operating at an inside gas leak: A: If the natural gas meter displays any readings at the building entrance/first floor, the Ladder Company Inside Team should go directly to the basement/cellar to investigate. Do not delay by going to a caller on an upper floor. B:If the leak is found and can be controlled by a valve or, on a low pressure service (or medium/high pressure service AFTER the service regulator) by taping/plugging, then do so. THE REGULATOR IS WHAT BRINGS A HIGH/MEDIUM PRESSURE GAS SERVICE DOWN TO LOW PRESSURE. SO AFTER THE REGULATOR IT WILL BE LOW PRESSURE NOT BEFORE THE REGULATOR DOES NOT WORK ON M/H PRESSURE C: If the leak is found and levels can be kept at less than 80% LEL by venting, you may continue to operate. D: If it is suspected that natural gas has been leaking for a considerable amount of time and is likely trapped in a void space, treat the AFFECTED area as a "potential blast zone." Natural Gas Pg 32

Do NOT use candle wax, paraffin or grease to lubricate a telescoping ladder. If lubrication is required use a silicone-based furniture polish (such as Pledge) on the beams of the ladder. Never use WD40 or similar oil-based lubricants, as this may clog the mechanisms inside the ladder.

Which of the following CIDS entries CORRECTLY describes an existing 4-Story Frame Multiple Dwelling that was renovated using lightweight metal C-joist with an added 2-Story, 10x20 setback in the rear? MJALT - 4 STY - 25X80 - CL4LW FD Designation "MJALT" (MAJOR ALTERATION) should be utilized for existing structures which have extensive alterations that involve HORIZONTAL EXTENSIONS, VERTICAL EXTENSIONS, or extensive changes to the structure changing its occupancy or purpose. Added extension in the rear is the Major Alt. A Wood Frame structure which is constructed, renovated, or repaired using any type of structural Light-Weight materials should be classified as CL4LW.

ENGINE OPS A: At least one bed must contain 6 lead lengths of 1 ¾" hose. B: At least one bed must contain only 2 ½" hose. C: At least one bed must contain only 3 ½" hose. D) The lead length of all hosebeds with either 1 ¾" hose or 2 ½" hose must be maintained with a STRAIGHT-STREAM nozzle attached. NO FOG NOZZLE TO THE RIGHT D Note: These hosebeds are intended for fire attack. Eng Ch 2 8.2, 8.3

Laddering a Brownstone with portable ladders presents specific challenges to operating members.: A: Placing a portable ladder at the window of the small room over the front entrance door will be difficult because of the long, high stoop, which may interfere with firefighting operations. Consider placing the ladder at the adjoining window to gain entrance to this small room. B: There may be 2 doors to the small room over the front entrance door; one from the interior hall and one from a larger adjoining bedroom. If there is no door leading into the small room from the large bedroom and hallway fire conditions prevent normal entry into the small room, access may be gained by BREAKING THROUGH THE LATH AND PLASTER PARTITION between the two rooms. C: **Some Brownstones have small, ELEVATED OR DEPRESSED COURTS in the front of the building, adjacent to the stoop. They generally have a small wall or iron railing around them, creating additional obstacles. D: In most cases, taking the ladder through the second floor (parlor floor) of an adjoining brownstone and passing it out the rear window to another member in the yard below is faster than using the fire building. It is important to take the ladder through with the BUTT facing the rear of the building Lad 1 10.2

During a Positive Pressure Fan operation the ventilation group supervisor shall instruct ventilation group members to survey the attack stairs below the fire to verify that doors in the stair enclosure are maintained closed, unless operating hoselines are stretched through the door. Which companies shall verify that stair doors are maintained closed above the fire? 2nd and 3rd Ladder companies AUC 349 sec 7.3

Drager PAC 6500 CO Meter: The on/off function is disabled. The only button to be used is the green "OK" button to silence the alarm, The CO meter shall be affixed to the HT strap ABOVE the remote mic., When reading EXCEEDS 2000 PPM, will display "rrr", The CO Meter will retain the highest reading the meter has been subjected to, however, this peak reading is NOT TO BE RELIED ON or used during any operation or incident. Good: because the meter is always on, this peak reading is not to be relied on or used during any operation or incident. INITIAL READING AND FRONT DOOR OF PREMISES

During a fire in an under-river tube between Manhattan and Queens, a ladder company that has been assigned to evacuate passengers by walking them on the track area would be correct to: a. STANDPIPE OUTLETS (NOT SECTION VALVES) are numbered and CAN BE USED TO PINPOINT locations through out the tubes b. Walk in the area OUTSIDE the rails. Drainage troughs are located between the rails making it unsafe c. The SQUARE underground tunnel section connects to the ROUND under river tube at the location of the entry/exit point of the tube. d. Be aware of 1,000 volt electric lines that run along the ceiling level which will not be deactivated by routine requests for power removal.

Collapse operations may require many specialized units: A: The Con Edison Vacuum Truck may ONLY be used by TRAINED MEMBERS of SPECIAL OPERATIONS COMMAND, in conjunction with the Con Ed operators and at the direction of the Incident Commander. B: Special Operations Support Ladder Companies shall not attempt or assist in tunneling and victim removal. C: SPECIAL OPERATIONS SUPPORT Ladder Companies MAY ASSIST Rescue Companies in tunneling and victim removal. D: ONLY a COMMAND CHIEF can request the response of the PODS Collapse 10.1.11, 10.1.12, 10.1.16

During company drill in lower Manhattan, the covering Chief made a few comments regarding older cast-iron lofts: A: If a loading dock is present, freight elevators may be found 20 feet inward from the front of the building. B: Freight elevators will not be installed with Fire Service capabilities. They are not initially used during fire operations due to their proximity to rubbish removal areas which are commonly fire origin locations. After evaluation and approval for use by the Incident Commander (IC), these elevators will allow for greater movement of members, tools and equipment due to their large size. C: When elevator shafts face the street, any window serving the shaft is required to display a "SHAFTWAY" sign across the OUTER portion of the window that is clearly visible from the street. AVOID placing aerial or portable ladders to these shaft windows or operating streams into them UNLESS visible fire is extending up the shaft. D: In many loft buildings, elevators doors can look like apartment entrance doors and often, elevator doors do not slide into the shaftway but swing out onto the loft floor as two separate doors or as a single-hinged door. Members must be alert when forcing a door, that it does not access an elevator shaft.

First alarm units are responding to a reported train stuck in an under-river tube. The Lieutenant in Ladder 500 has the following thoughts about the sound powered phone system: A: In the street to tunnel sound powered phone system coverage includes a particular under river tunnel or tubes (both directions) and a location on both sides of the tunnel, typically the nearest emergency exit. IN THE STREET TO STATION SYSTEM COVERAGE INCLUDES A PARTICULAR STATION AND THE STREET ABOVE B: There is usually no connection from one sound powered phone system to another (e.g., from and under river tunnel system to a nearby station.) C: Headsets are preferred for use throughout the NYC transit system, due to the high noise levels that may be encountered. D: In under river tubes, sound powered telephone connectors are found at standpipe outlets; approximately 200 FEET APART.NOTE "A": IN THE STREET TO STATION SYSTEM COVERAGE INCLUDES A PARTICULAR STATION AND THE STREET ABOVE TB Tools 31 4.1.1, 4.1.2, 4.1.3, 4.3.2

During multi-unit drill, Lt. Dillon had his members stretch a hose line up an aerial ladder into the 3rd floor of a vacant building: A: The nozzle firefighter left her length on the ground and carried the nozzle with the hose playing out behind her. The hose was carried under her left arm and the nozzle draped upward across the front of her torso and back over her right shoulder. B: Once the nozzle firefighter reached the destination, she momentarily passed the nozzle to the engine officer, allowing her to safely dismount the aerial. C: The back-up firefighter climbed the ladder behind the nozzle firefighter, advancing hose as they climbed. The hose was maintained on the LEFT side of the aerial ladder. Note: The engine officer will wait until ALL of the firefighters are OFF THE AERIAL before calling for water in the line. The line should be charged gradually. D: When sufficient hose was stretched, a hose strap was used to secure the hoseline to a rung of the aerial ladder at the WINDOW LEVEL. Once secured, all members on the aerial completed their ascent up the ladder and proceeded to the point of operation. Eng Ch 7 9.5, 9.6, 9.7, 9.10, 9.11

A: An Urgent Message from the 1st Due Engine Chauffeur following the Loss of Water supplying the 1st & 2nd lines at an MD fire. REQUIRES EMERGENCY ROLL CALL B:An Urgent Message from the Roof Firefighter indicating a Danger of Collapse in the rear of a taxpayer. DOES NOT REQUIRE EMER. ROLL CALL

During operations at the scene of an MVA with a victim pinned: A:The ENGINE OFF should divide the company into two teams. The officer and two CFR FF (equipped with trauma bag and cervical collars) proceed to the scene of the accident. B: When a fire or hazardous condition exists, STRETCHING AND CHARGING A HOSELINE IS PARAMOUNT. CONSIDER A FOAM HANDLINE C: THE ROOF AND OV bring the Hurst tool equipment to the scene of the accident and initiate the operation Disentanglement & Extrication 4.1, 4.2

Beluga auto glass knife : A: There is no need to constantly remove and restart your cut to reposition the cutting head or drill battery. B: The blade reciprocates UNDER the glass, crushing it while pushing the bulk of the debris AWAY FROM the vehicle compartment. C: The knife is designed to cut laminated safety glass found in automobile windshields, HURRICANE WINDOWS and BOTH RESIDENTIAL AND COMMERCIAL CONSTRUCTION GLASS D: Depending on the drill speed you select, the Beluga can cut about as fast as you can push it. TB Tools 39 2.1, 3.2, 3.4, 3.9

ENGINE OPS In the event the advance of the hoseline is stalled due to insufficient available hose, the back-up firefighter may need to momentarily leave the nozzle firefighter to retrieve the hose necessary to continue the fire attack. This must be coordinated with the officer and nozzle firefighter. In larger apartments or private homes, the door firefighter may be forced to move into the fire area to keep line of sight with the nozzle team. Maintaining VISUAL CONTACT with the nozzle team is necessary as they advance. If the 2nd engine arrives after the 1st engine has begun stretching, the 2nd arriving members should begin assisting with the stretch only AFTER they have confirmed the position of the 1st arriving engine and the progress of the stretch. This may require the 2nd arriving members to enter the building and follow the line to determine progress. CONTROL FF MUST REMAIN LAST IN STRETCH, EVEN IF ASS. BY ANOTHER UNIT Eng Ch 6 3.10, 4.5.5, 5.5.1, 6.3

H-type fires: A: A FIRE ESCAPE IN THE THROAT OFTEN SPANS THE FIREWALL and indicates TWO SEPERATE APTS IN THE THROAT B: One apartment in the throat may span firewall with NO FIRE ESCAPE and have TWO interior exits, one to the stairway in one wing and the other to the adjacent wing. Usually, one door is nailed shut or obstructed by furniture so as not to be openable. C: Some buildings have been found to have a FIRE PARTITION IN THE THROAT which does not extend completely to the REAR WALL. When a fire partition is found, it must be checked to be sure it is carried to the FRONT AND REAR FIRE WALLS D: Ceiling beams are not always laid in the conventional manner (across the WIDTH OF THE WINGS). Some may be laid lengthwise, depending on the iron framework. MD Ch 1 4.10.3, 4.11.3-4.11.5

ENGINE OPS TWO lengths of 1 ¾" hose to be used as a "booster line" for outside fires, such as rubbish fires or car fires. This hose should be maintained with a fog nozzle attached to one length. Note: In an emergency, it can also be used to apply water from the exterior of the fire building. It should be maintained pre-connected to a discharge outlet. It MAY also be maintained pre-connected to a gated wye attached to a discharge outlet. This hose may be maintained either rolled or folded. Generally, it is stored on the front bumper of the apparatus. Eng Ch 2 9.3, 12.1

POW A: When fire is found to involve the TRUSS SPACE, exterior operations should be the primary tactical consideration. B: Consider the use of search ropes due to the large floor areas of these structures.

Engine 244 goes out on a single unit Class E response for an alarm activation in a commercial building. Upon arrival they receive information that indicates there may be a fire on an upper floor. The box is filled out with Engine 256, Engine 269, Ladder 171, Ladder 177 and Battalion 70. It is determined that the building has an ARCS system which will need to be activated to enable communications. Which officer ensures notification is made to the Dispatcher for re-transmittal to all incoming units if the proprietary repeater system has been activated? First Ladder Officer

Operations with the Honda Generator requiring maximum output should be limited to ______ minutes. 30

Engine Company 4, in lower Manhattan, is returning to quarters after a response when they are flagged down for two pedestrians struck near the South Street Seaport. Both patients are in critical condition and the officer decides to contact the EMS Dispatcher directly via the apparatus radio. a. Contact EMS on the proper EMS borough frequency for non-MCI incidents. Use EMS-Citywide for MCIs or if the borough frequency cannot be determined d. Notify the FDNY borough dispatcher of all appropriate signals, progress reports and unit status. (Communications Chap.14 Add.1 2.5, 2.6, 2.7)

PROBIE Control Sheet- Inside cover of the Proby Folder Tool List- stapled to 1st page of notebook Monthly Training Quiz- Staple it into their notebook AUC 323 sec 2.4, 2.5, add 2 sec 1.3

FAST UNIT A ladder company will be designated as the FAST unit upon transmissions of signals 10-60, 10-66, 10-75, 10-76, and 10-77. THE IC CAN HAVE THE FAST UNIT PROVIDE ADDITIONAL EGRESS ROUTES WHILE STILL MAINTAINING UNIT INTEGRITY, E.G., REMOVE WINDOW BARS, PLACE PORTABLE LADDERS. Managing Members in Distress Ch 2 2.1, 2.2, 2.3, 4.5

Department Chauffeurs and Tiller operators should NOT insert their thumbs through the wristlet loops of bunker coat prior to driving apparatus. PPE - AUC 310

FIRE DYN B: The lower explosive limit (LEL) is the lowest concentration by volume of flammable gas in air that will support flame propagation. This is also known as lower flammability limit. C: The upper explosive limit (UEL) is the highest concentration by volume of flammable gas in air that will support flame propagation. This is also known as upper flammability limit.

Select the choice that shows proper understanding of FDNY CFR protocols: a. **If a CFR-D Unit arrives on scene and NYPD ESU has already initiated patient care, the CFR-D officer shall ascertain from ESU if any assistance is required from the CFR-D unit. If no assistance is required the officer shall transmit a 10-91 and go 10-8, REGARDLESS if ESU has a working DEFIB or not. If FDNY ARRIVES FIRST, and then ESU arrives and they want to take over patient care, then we have to be sure that they have a WORKING DEFIB before handing the care over to them c. The telemetry phone number will be found on the chart holding the PCRs (CFR Chap.2 4.13.1, 4.17, 5.3, 6.1.1)

FOAM A: Ladder companies have limited foam capabilities. They are limited to 2 ½-gallon hand-held AFFF extinguishers. B: Ladder companies are required to carry two five-gallon containers of AR-AFFF (red band) foam concentrate to be used by Engine companies. C: Each Engine company must carry at least three five-gallon containers of AR-AFFF foam concentrate, a handline foam eductor which flows 125 GPM, and an AERATING FOAM nozzle.

The drag rescue device incorporated into the bunker coat can be used for which type(s) of removal? Horizontal drag only Explanation:THERE IS A CONFLICT ABOUT DRAGGING UP STAIRS. MMID CH 3 ADD 2 2.1 "NOTE" SAYS MEMBER SHOULD NOT BE DRAGGED UP STAIRS UTILIZING THE DRD. MMID CH 3 ADD 4 2.3 SAYS AFTER THE DRD IS SECURED AROUND THE RIGHT SHOULDER STRAP OF THE SCBA IT CAN BE USED TO MOVE MEMBERS UP OR DOWN STAIRS."A" WAS STILL THE ONLY GOOD CHOICE, THE DRD CANNOT BE USED FOR VERTICAL LIFTS. JUST BE AWARE OF THIS CONFLICT.Managing Member in Distress Ch 3 Addendum 2 2.1

Ice accumulations on an unsupported aerial ladder under certain conditions may lead to twisting and possible collapse of the ladder: A: When ice prevents the chauffeur from raising the aerial ladder away from a building, the hydraulic mechanism may be assisted by placing a portable ladder under the extended ladder and using a number of members to exert additional pressure. B: At a high ladder angle, in addition to using a portable ladder under the extended aerial ladder, consider exerting additional pressure with a UTILITY ROPE. The rope is tied near the tip of the ladder and members on the roof or in the window of a building across the street pull the rope taut in order to assist the hydraulic power. C: When ice prevents retraction of ladder sections, care must be exercised to avoid damaging the rungs or weakening the cables. A heavy coating of prescribed lubricant will inhibit the formation of ice at critical points and will also facilitate deicing. D: In sub-freezing temperatures, drain ladder pipes, hose, piping, siamese connections, etc., as soon as the stream is shut down. Lad 2 8.19.1 - 8.19.5

If a hoseline is short stretched from a standpipe with a lead length of 2" hose, certain actions should be taken to add a length to the front: A: The 1" MST is REMOVED to allow the connection of an additional length. B: The additional length can be either 2" hose or 2 ½" hose, so an INCREASER will be needed to make the connection C: It IS permissible to add a 2nd length of 2" hose (with 1" tip) to remedy a short stretch. D:It is permissible to add a length of 2 ½" hose (with 1 1/8" tip) to a lead length of 2" hose. Eng Ch 10 4.3.10

In order to prevent slippage of the butt or movement of the top of a raised portable ladder, it is important that it be butted by a member.: A: In any case for fire, emergency or rescue work, a butt firefighter shall be used to stabilize the ladder and prevent slipping. B: The butting member places their LEFT FOOT in the center of the bottom rung of the ladder and maintains a downward pressure. Their RIGHT foot is positioned behind them at a comfortable distance to maintain balance and provide resistance against ladder movement C: Both hands of the butting member are placed against and grasp the ladder beams to aid in steadying the ladder. D: If a member is working off one side of the ladder, the butt firefighter moves their foot from the center of the bottom rung of the ladder to the side opposite the one from which the firefighter is working, and places their foot next to the beam. ad 1 7.5.1

When approaching a vehicle with a possible chemical suicide: A: Person's skin tone may be RED in color B: Person may be wearing gloves or swimming goggles C: Tape may be placed around vehicle's windows or doors, or use of plastic to contain the vapors D:Presence of chemical containers or strong chemical odors, such as hydrogen SULFIDE/FLORIDE have an odor of ROTTEN EGGS Haz-Mat 11 sec 3.2

In order to vent natural gas to open air, FDNY personnel are allowed to pull rectangular or square electric manhole covers under which of the following conditions? A:FDNY personnel shall not pull these covers. CHOICE "D" IS NEEDED TO PULL ROUND ELECTRIC MANHOLE COVERS. *FDNY PERSONNEL DOES NOT PULL SQUARE OR RECTANGULAR ELECTRIC MANHOLE COVERS* Natural Gas 9.2.4

LW PD When the fire is of such magnitude that it cannot be quickly knocked down with the TWO HOSELINES, then an OUTSIDE OPERATION must be considered. NOT: alternative strategies (i.e. KO Curtain, breaching wall, etc.) must be considered.

In what way do wood braced-frame constructed buildings collapse? Inward/Outward Collapse B) Curtain-Fall Wall Collapse - Exterior MASONRY wall drops like a falling curtain cut loose at the top; the collapse of a brick veneer, brick cavity or masonry-backed stone wall. The impact of an aerial platform master stream striking a veneer wall at close range can cause a curtain-fall collapse of bricks. C) Ninety-Degree-Angle Wall Collapse - A type of building wall collapse; the wall falls straight out as a monolithic piece at a 90-degree angle, similar to a falling tree. The top of the falling wall strikes the ground a distance from the base of the wall that is equal to the height of the falling section. Bricks or steel lintels may bounce or roll out beyond this distance. D) Tent Floor Collapse - A floor collapse in the shape of a tent; when a floor collapses and an interior partition or wall holds up the center of the fallen floor. If the interior partition were not present, the result would be a pancake collapse.

In order for FDNY members to operate inside the warm zone during an Active Shooter Incident (Aggressive Deadly Behavior), members must seek approval by whom: Deputy Chief FDNY members shall only operate inside the warm zone when requested by the NYPD. This operation must be approved by a FDNY Deputy Chief, unless the NYPD IC requests entry for immediate life-saving medical intervention ERP add 3A sec 7.5

Kernmantle Life Saving Rope: A: FOR LOWERING OPERATIONS, the KLSR will be used in conjunction with a mechanical decent control device (DCD), presently the Petzl I'D NOT TO BE USED WITH SINGLE SLIDE B: FOR THE SINGLE SLIDE EVOLUTION, four turns on the personal harness hook are required NOT FOR LOWERING OPS C:A Kernmantle LSR subjected to the weight of two people shall be placed out of service forthwith and replacement requested. D: The Kernmantle LSR shall be used only for life saving PURPOSES. IT SHALL NOT BE USED FOR DRILL PURPOSES TB Rope 10: 3.1, 3.2, 4.0, 4.2

Roof Firefighter at a fire in a multiple dwelling is responsible for communicating vital pieces of information to the incident commander. The Location of stairways, fire escapes and party wall balconies.

Ladder 300 has young firefighter working her first tour of the one year rotation. After roll call, members are going over the operation of the power saw and make the following comments: A:During roof or floor cutting operations, everyone in the vicinity of the saw in operation shall observe as near as possible and practical, a 20 foot radius circle of danger. B:Use of the power saw from a ladder (EXCEPT A TL) IS NOT RECOMMENDED C: Only the officer, the operator, and the member designated as the guide may enter the circle of danger. D: The saw shall always be shut down when unattended. TB Tools 9 4.7, 4.7.1, 4.8.3, 4.14.2 Note

Upon the discovery of a new cell site on one of your buildings can be found in which choice: A: The administrative company must notify their battalion, division, and all first alarm units via telephone followed by written memo B: The administrative company must do an on site inspection and evaluate the cell site C:The administrative company should complete and submit a CIDS card and forward it to their battalion fire prevention coordinator CIDS card should specify: - Location of the cell site room - Backup power supply location - Shut offs - Emergency phone number of the cell phone company AUC 331 sec 4

Ladder Company 171 was assigned to a Class E Alarm in a 15-Story hotel. Upon arrival, they discovered the alarm is for a CO detector in room 707 on the 7th floor: A: All members except the chauffeur accompanied the officer into the building lobby. B: If the alarm is determined to be a CO detector activation, the officer shall notify the dispatcher, then investigate the area of activation REGARDLESS of alarm status. DO NOT GO FOR RESET C: NO ELEVATOR, 7TH FL D:The officer transmitted a 10-38 code 3 after getting readings of 10 ppm on the CO meter. Explanation:COMMUNICATIONS MANUAL - CHAPTER 6 ADDENDUM 2

It is the change of tours and the new Lt. is exchanging information with the incoming captain. He is briefing him on an immediate CIDS he had entered for a building in their district: A: The officer used the eCIDS application to enter the proposed CIDS. FAXED PAPER COPIES ARE NO LONGER ACCEPTED B: After submitting the immediate CIDS, the officer notified the ADMIN BC WHO WILL NOTIFY THE DC WHO NOTIFIES FDOC C: Submission of an immediate CIDS generates an AUTOMATIC EMAIL notification to THE NEXT LVL OF NECC APROVAL. D: Immediate CIDS entries will always appear at the TOP of a unit's pending list and be in BOLD print. COMMUNICATIONS MANUAL - CHAPTER 4

Ladder Company members should be aware that, at vacant building fires, safety is of the utmost importance: A: Primary searches should generally be conducted after all visible fire has been knocked down and the IC has completed a size-up and risk assessment. Members may vary from this guideline when confronted with a known life hazard. B: Members shall not conduct searches on the floors above the fire until all visible fire has been knocked down and the IC has conducted a size-up and risk assessment. Members may vary from this guideline when confronted with a known life hazard. C: Form a habit of climbing stairs by placing the MIDDLE of the foot above the step riser and stepping as close to a SUPPORTING WALL as possible. Placing downward pressure on risers and climbing close to supporting stringers is the safest way to climb stairs. These areas are the most structurally stable areas of the staircase. D: When the stability of a stairway is in doubt, members should place an extension ladder over the stairway, ensuring that it is properly supported at both the top and bottom. Vacant 5.3, 5.4, 6.2

The gear bag should be placed in double (two) clear bags, tied or taped closed An EDR-1 shall be completed and placed in between the two bags, facing outward, for identification purposes. Bagged items shall be left, if possible, in a light-traffic area adjacent to HW for pickup by the DSU AUC 310 add 4 sec 2

Lieutenant Casey is working in Ladder 400 when Firefighter Jones knocks on the door and informs her that his PSS is damaged and needs to placed out of service: A:Made an immediate phone notification to the ADMINISTRATIVE DIVISION and requested a replacement PSS B: Directed Firefighter Jones to use the spare PSS from the PSS repacking kit while awaiting his replacement PSS. C: Informed Firefighter Jones that if a response was received while he was not equipped with a PSS, he may still respond with Ladder 400. THIS MEMBER WILL STILL RESPOND WITH THEIR UNIT. HOWEVER, THE MEMBER WILL NOT BE COUNTED TOWARDS THAT UNIT'S STAFFING AS IT RELATES TO THE PROVISIONS OF AUC 287, SECTION 8 (REDUCED STAFFED/UNDERSTAFFED UNIT). AT AN INCIDENT WHERE THE MEMBERS WILL BE OPERATING IN AN IDLH AREA, THE MEMBERS NOT EQUIPPED WITH A PSS SHALL NOT ENTER/OPERATE IN THAT AREA D: Completed an Out of Service Life Safety Equipment Report (SCF-2) and forwarded it through the chain of command to the CHIEF OF SAFETY If the pss bag or any component shows sign of heat exposure, the whole system gets put oos (Rope included whether it's exposed or not) If the bag gets grossly contaminated from other than fire ground contaminants, and the rope is not affected, only the bag gets put oos TB Rope 4 6.1, 6.2, 6.9, 6.15

On the transmission of the next higher alarm, which is part of the signal 10-66, all the following units of shall be directed by the dispatcher to report to and remain at a staging area until ordered to the scene: 1) Rescue 2) Squad 3) SOC Support Ladder 4) FAST Unit 5) CFR Engine

Listed are several items that may be presented to a CFR in the prehospital setting: 1) Out-of-hospital DNR form 2) DNR bracelet 3) Expired or non-expired Hospital/Nursing home DNR Form 4) MOLST form without a DNR order. Which ones may be accepted as a valid DNR? 1 & 2 only Explanation: 3) NON-EXPIRED ONLY IN HOSPITAL 4) MOLST FORM WITH A DNR ORDERCFR Ch 2 Addendum 1 4.1

Chief Blue stopped by Engine 100 for company drill and made a number of comments about the features of Brownstones and how they affect fire operations: A: Immediate ventilation, entry, isolation and search (VEIS) of the top floor is mandatory, and is considered to be one of the most important operations at these fires. B: Doors at the top of the cellar and first floor (basement) stairs normally prevent the immediate extension of cellar fires up the main interior stairs. However, there will be a rapid build-up of smoke and heat on upper floors. C: There are LIMITED means of venting the cellar. The MOST THAT CAN BE EXPECTED are a couple of very small windows at ground level in the rear, an opening under a grating near the first floor (basement) vestibule, and possibly a coal chute D: In some cases, rear extensions have been added on the first floor which may be TWO - THREE stories in height and 10 to 20 feet in depth, with their own cockloft. BS/RF 2.2.9-2.2.12

Listed below are some characteristics of steam and the steam system in NYC: A: Con Ed IS NOT the only entity generating high pressure steam in NYC. DISTRICT STEAM SYSTEMS SHOULD BE ENTERED INTO CIDS PROGRAM B: Low pressure AND HIGH pressure steam IS USED IN BUILDINGS FOR A NUMBER OF PURPOSES E.G., TO PROVIDE HEAT AND HOT WATER, TO HEAT FOOD, RUN AIR CONDITIONERS . C: Steam is invisible. D: Water slugs can be pushed through piping by the steam at speeds as high as 200 MPH

Smoke may present itself in many colors: A: GREY SMOKE indicates that at least some flaming combustion or smoldering combustion is present. B: The further the smoke travels, the more carbon it can lose, resulting in a GREY SMOKE C: DARK SMOKE that has travelled some distance can COOL AND LARGE CARBON PARTICLES suspended in the smoke can ADHERE TO SURFACES. D: In a building issuing dark smoke from some areas and grey smoke from other areas, usually the areas with GREY smoke are remote from the fire. TB FD Ch 2 3.5.4 C

MEGA - OVER 800', NOT 800 OR MORE

All members should be familiar with fire protection features of high rise office buildings. A: The fire command station will be located in the lobby of the building, NEAR THE ELEVATOR CONTROL PANEL. B: A FLOOR WARDEN STATION shall be located on each floor between the required exits. C:At least one manual fire alarm sending station shall be located in each path of escape in each story of a building. Additional stations shall be installed so that no point on any floor shall be more than 200 FEET from the nearest station. D: An approved combustion ionization detection device or a combination of an approved smoke detecting device and an approved fixed temperature thermostatic device shall be installed at each elevator landing and within the HVAC system. HROB 7.2.1 A, 7.2.3, 7.2.4, 7.2.5, 7.2.6

Members just returned from a reported fire in a factory which turned out to be unfounded. However, when checking the rear, the OV in the truck encountered a double bar fox lock on the rear door. A: These locks are easily recognizable by the location of the cylinder in the center if the door. B: Cylinders are usually covered with a metal plate with four bolts. C: Using a halligan, shear off the top two bolts and one bottom bolt, then turn the plate down exposing the lock cylinder. D: After removing the cylinder with the K TOOL, use the SQUARE KEY TOOL and turn the tool towards the BOTTOM bar thus unlocking the door TB Forcible Entry 1 4.2 B #6

At motor vehicle emergencies, the goal of vehicle stabilization is to prevent rocking of the vehicle: A: Check under the vehicle for victims before any stabilization methods are taken. B: Vehicles found on their side or roof shall be secured to a substantial object (apparatus, tree etc.) with a UTILITY ROPE C: When deflating tires use vice grips or pliers to remove the valve stem. D: When stabilizing vehicles on all four wheels, place chocks just behind the front wheels and in front of rear wheels, step side down. Disentanglement and Extrication 5.3, 5.4, 5.5, 5.6

Members may encounter difficulties when connecting hose to a Fire Department Connection (FDC.) This can include defective/damaged threads, frozen/stuck swivels and broken valves: A: Tapping the swivel(s) on the FDC with a tool (spanner) may loosen paint, dirt, etc., and allow the swivel to operate. B:Twist the supply hose 4-5 TURNS TO THE LEFT, insert the male end, then twist the male end to the right (clockwise) into one of the female swivels of the FDC. C: Insert a 3" x 3" x 3" Siamese into one of the FEMALE SWIVELS of the FDC, which provides a female coupling for the male coupling of the 3 ½" supply hose to attach to. D: Attach a 3" double male fitting to the malfunctioning female coupling of the FDC and then couple a 3" double female fitting to the double male to provide a female coupling for the male coupling of the 3 ½" supply hose to attach to. Eng Ch 5 4.3.4

FAST PAK The HIGH PRESSURE SIDE of the bag contains a 4500 psi Scott air cylinder (15 MINUTES of use).

Members of an elite study group were discussing radio signals and several statements were made about the 10-70 code: A:The transmission of a 10-70 requires an "urgent" HT transmission to all units on the scene. B: The transmission of the 10-70 shall be an "urgent" message to the dispatcher from the UNIT transmitting the signal D: No Water/Insufficient Pressure at a Standpipe Outlet (NOT SPRINKLER SYSTEM) warrants a 1070 signal.

You are first to arrive for smoke in a subway station. After an investigation you discover there is a small rubbish fire under the platform. Before extinguishment operations commence, you make sure of all of the following procedures are adhered to. A: Power is removed B: Confirmation of power removal must be by FDNY dispatcher C: Members are posted at EACH END of platform to act as safety people D: An alternate area of refuge is assured in case of train movement AUC 207 sec 5.3

Members responded to a reported fire in a high rise office building with several elevator banks. After determining the "B" bank provided the best access to the fire area, units initiated a phase 1 recall of the fireman service elevators in this bank.: A: All elevators IN THAT BANK will be returned to the street lobby or terminal floor. B: The "emergency stop" buttons will be rendered inoperative. C: An elevator traveling away from the street floor or from its lowest landing will REVERSE DIRECTION AT THE NEXT LANDING WITHOUT OPENING ITS DOORS, AND RETURN NON-STOP TO THE STREET LOBBY OR TERMINAL FLOOR D: All door reopening devices for power operated doors shall be rendered inoperative EXCEPT FOR THOSE MECHANICALLY ACTIVATED BY A SAFETY EDGE Emergencies 1 5.3.1 D

Con-Ed electrical facility: A: Handlines shall never be used on energized electrical components at Con-Ed facilities, EVEN WITH FOG NOZZLE B: The primary means of applying water to energized electrical components is through the use of a Tower Ladder C: Once a Tower Ladder is approved for use, the safe operation position for the TL will be determined in conjunction with Con-Ed personnel. Once determined, all members are removed from the apparatus including the basket and turntable D: The Aqua Stream Master Stream nozzle shall NEVER be used on an Aerial Ladder or an Engine deck gun Explanation:AUC 338A

Members should be aware of features of nonfireproof multiple dwellings; some of which differ depending on when they were constructed: A: To avoid being required to be built of fireproof construction, new law tenements built between 1916 and 1929 had floor areas broken up into areas of 2,500 square feet or less. Dividing walls only went as high as the CEILING of the TOP FLOOR NOT: underside of the roof boards. D:After 1929, the size of the area to be enclosed by fire walls in nonfireproof multiple dwellings (AKA apartment houses) was 3,000 square feet. MD Ch 1 1.3.2, 1.4.3

Question 34:At a recent fire operation consisting of a fully involved brownstone, with extension into exposure 2, upon unit arrival: A: The first arriving engine company dropped two hoselines in front of the fire building and positioned the apparatus for the possible use of the multiversal nozzle or to supply a TL. B: The first hose line advanced into the fire building. C: The second hose line advanced into the FIRE BUILDING as a back-up hoseline. D: The third hose line was stretched as ordered by the Incident Commander into exposure 2. As ordered by the IC, the third hose line may be: FEX EX 1. Advanced into the fire building. 2. If fire is reported in an exposure, stretched to that exposure 3. If there is no fire in the exposures, stretch through an exposure to the rear yard of the fire building.BS/RF 3.4

Members should be aware that the actual length of the life-saving-rope may be less than the nominal length of 150 feet due to natural shrinkage after several years in the field. Over a period of time some ropes have shrunk ______ feet. A hockle reduces the strength of a rope by _____percent. 8 to 10; 40 to 50

If a vent pipe placed over a manhole has a _____ stripe on ____ of it, this indicates that the steam is the result of a water leak, not a leaking steam main. BLUE AT THE TOP

Mill Lofts: A: Heavy timber floors consist of plank floors, 3 inches thick, laid directly onto beams and girders which are a minimum of 6-inches in any dimension. These floors were covered with 3 layers of resin sized building paper, mopped with tar and topped with a 1 ¼ inch, hard wood finished floor. Total floor thickness averages at least 4 inches. Note: Cutting and opening these floors to facilitate the placement and operation of cellar pipes and distributors will be manpower intensive. B: The UNDERSIDE of the floors are normally left EXPOSED. C: Girders resting atop wooden or cast-iron columns are sometimes joined together using metal brackets (dog-irons) on both sides, providing marginal enhanced stability. D: A general rule of thumb for the run of original hardwood finished flooring is from the FRONT to REAR of the building. A firefighter lost on a floor can utilize this knowledge to find a FRONT or REAR means of egress. Lofts 5.3.3

Members must be familiar with the knots and hitches required for the proper deployment of the KLSR: A: There is no set predetermined number of wraps for tensionless hitch. B: The KLSR system requires the use of the figure eight knot with a bight of approximately 10"-12", and a tensionless hitch. C: The bowline-on-the-bight with a slippery hitch might be required for use with the KLSR. D: The RED ANCHOR CARIBENER MUST BE PLACED ON THE ROPE LEADING BACK TO THE KLSR. The red anchor carabiner CANNOT HANG FREELY. TB Rope 5 Addendum 1 1.1, 1.2, 2.1.3 Note, 2.10 Note

NATURAL GAS WHEN UNABLE TO LOCATE THE SOURCE OF THE LEAK, DO NOT SHUT POWER.

Members operating on the fire ground in other than their assigned unit must wear a temporary front piece to properly identify themselves in the unit they are working in that tour: A: All Engines, Ladders, Rescues, and Squad companies will be issued 1 temporary front piece for the company officer B: All Engines, Ladders, Rescues, and Squad companies will be issued 3 temporary front pieces for the firefighters C: At the completion of the tour, temporary front pieces are to be RETURNED TO HW D: An 11"X17" sign, which reminds detailed members to return the front pieces shall be placed in an area, clearly visible to all members leaving quarters Lost front pieces shall be the subject of a lost property report (FS-112) and forwarded through regular channels. Any member finding a temporary front piece shall place it in the department bag for delivery to proper unit AUC 299

Natural gas system infrastructure: A: Gate station facilities have remote monitoring by the Utility Companies Gas Control Centers but generally have no on-site personnel. B: Natural gas is piped to customers along distribution mains which are HIGH, MEDIUM OR LOW PRESSURE C: HIGH PRESSURE distribution mains are made of STEEL OR PLASTIC D: MED & LOW PRESSURE distribution mains are made of STEEL, PLASTIC or, if OLDER, CAST IRON Natural Gas 4.1, 4.3

At a fireproof high rise multiple dwelling fire where the fire is confined to the stairwell: A: If, upon arrival at a stairwell door, there is a light smoke condition present, immediately close the door to the stairwell. Notify the IC of a smoke condition in the stairwell and identify the stairwell. B: Proceed via the CLEAR stairwell to search for the source of smoke, one floor at a time. Another unit can begin searching for the source of smoke from the lower floors upward, one floor at a time, using the CONTAMINATED stairwell. Note: Due to the flammability of the paint, under no circumstances shall members operate above the smoke in the involved stairwell, until complete extinguishment of the burning material has been accomplished. Variation: In a low rise fireproof multiple dwelling with ONLY ONE STAIRWELL, once it has been ascertained that the cause of the upper floor smoke condition is from the stairwell fire, the search shall be conducted from the LOWER FLOORS UPWARD C: The roof firefighter shall proceed to the roof via the clear stairwell and vent the contaminated stair bulkhead from the roof. If flammable paint in the stairwell ignites, this will give it a place to vent and possibly prevent horizontal extension on any upper floors. D: When the source of smoke has been located, approach and extinguishment shall be made from the floor below, with either a can or a handline, based on the volume of burning material. MD Ch 6

OLT STORE FIRE A charged hoseline must be ready before the store is ventilated. It is especially important that no plate glass windows be broken without a charged line being ready. Note: Fires in stores may extend to the upper floors by auto-exposure or via openings in the store ceilings. These store ceilings were usually constructed of metal panels. The metal ceiling can communicate heat to the floor above.

Members operating at a steam high energy line break (HELB) in the street: A: Approach an outdoor HELB from upwind and stay clear of the vapor plume. B: Consider SHUTTING HVAC systems of nearby buildings C: Consider evacuating buildings from the rear or side entrances to avoid the exclusion zone. D: Prepare for decontamination of civilians, firefighters, bunker gear, tools, equipment and vehicles. Steam 4.2

Occupancies equipped with Lexan panels instead of conventional glass windows can present significant challenges to operating members. These windows may be forced with a portable ladder if at ground level: A: Remove the exterior screen, if present. B:Place the BUTT OF THE LADDER on the Lexan window in the CORNER ADJ. TO THE WINDOW FRAME C:THREE OR FOUR MEMBERS apply a gradual leaning pressure against the window until it is forced inward. D: If a section of window snaps off, continue forcing around the window perimeter until a sufficient opening has been made. ad 1 10.3.1

There are general precautions to take when operating inside a Con-Ed Substation. A: Do not force entry. Wait for the Con-Ed White hat B: Do not cut fences or force locked doors or gates This is written in bold C: Avoid bringing metal tools into the substation (including wood or fiberglass hooks) and do not allow tools to project above your SHOULDER D: When raising aerial ladders and tower ladder buckets. maintain a 18-foot safe clearance horizontally from the substation's exterior fence line AUC 338 add 2 sec 6

Operating in a high rise office building fire, if difficulty is encountered in clearing the attack stairway of occupants, the officer of the third arriving ladder company shall advise who to withhold the attack until the occupants have been safely removed? The first arriving ladder company or the Fire Sector Supervisor/Branch Director, if established. NOT THE IST ENGINE CO, NO MENTION OF IC

Which gas valve(s) mentioned below can only be shut down by FDNY members in consultation with the utility company: Curb Valve only Explanation:*NO MENTION OF CONSULTING WITH UTILITY FOR HEAD OF SERVICE VALVE* *FDNY MEMBERS ARE NOT PERMITTED TO SHUT THE MAIN VALVE* *THE CURB VALVE CAN BE SHUT BY FDNY MEMBERS AS A LAST RESORT AND IN CONSULTATION WITH THE UTILITY COMPANY* Natural Gas 6.7.3 #5, #6, #7

PD'S Windows with sills that are approximately CHEST HIGH may require a drop of 5-6 FEET to floor level. This presents a serious problem if fire conditions force members to exit via this window. B Note: Window Bars vary from aluminum child guards to heavy wrought iron and the method of installation and type of structure (brick, wood, etc.) determines how difficult removal will be. WINDOW BARS - brief description of the type of building involved and THE PRESENCE OF WINDOW BARS NOT EXACT LOCATION

SEARCH If fire is wrapping around the door jamb as the door is being forced open, a hoseline must be charged and in place at the door before the door is opened.

ROWFRAME There are many variations in the construction of these buildings. Light and airshafts are found in some, while not in others. Usually the buildings of longer length will have the shafts. Air and light shafts are of WOOD, and fire in shafts rapidly assumes blowtorch proportions. C: To gain entrance to the roof from the interior of the building, there is a scuttle on the roof which is reached by an iron ladder from the top floor. The scuttle is usually near the skylight over the stairs. D: The major defects or faults in the construction are the lack of the fire stopping and the vast quantity of combustible material used in the construction. The salient feature common to all, regardless of variations in design, is the common cockloft spreading over all the buildings in the row. This cockloft may vary in height from ONE FOOT to a height tall enough for a MEMBER TO STAND IN. BS/RF 5.2.2, 5.2.6, 5.2.7, 5.3.2

MAYDAY for a Collapse Imminent: A:The member becoming aware of the situation shall immediately depresses their EAB button and then contact the IC with the Mayday transmission. B: The member transmitting the Mayday must transmit The location of the Imminent Collapse and THEIR LOCATION (not the location of affected members) C: The IC shall ensure a roll call is conducted immediately AND ALL MEMBERS ACCOUNTED FOR

Second arriving engine at a high rise fireproof multiple dwelling fire: A: Upon arrival, ENSURE the Fire Department Connection is supplied and provide assistance where necessary (e.g., extremely long stretch to the FDC, broken FDC, frozen hydrant, etc.) B: Obtain the Post Radio from the first arriving BC and bring it to the standpipe outlet where the first hoseline is being connected to establish a communications link on the Command Channel between the fire sector and the IC, if necessary. C: The second arriving engine officer must advise the IC when their members are assisting the first engine advance into the IDLH. D) When the second line is charged ,the pressure on the first line may drop; therefore, the CONTROL FIREFIGHTER at the standpipe outlet supplying the first line AND the OFFICER of the first line should be notified.

Fire Window Blanket: a. The blanket is large enough to cover at least 2 windows if necessary. The bottom of the blanket is weighted to facilitate positioning. b. The SQUAD CO will deliver their Window Blanket to the floor below the fire when operating at a high rise fireproof MD. If it is to be deployed, the Fire Sector Supervisor will assign a unit. c. The UNIT ASSIGNED TO DEPLOY THE BLANKET MAY DEPLOY A SPOTTER to observe the deployment of the blanket from the exterior. d. Just before the blanket is put in place, the IC must make an announcement to all units. (TB Tools 3)

Smoking is prohibited in all Fire Department facilities at any time, without exception. Smoking is also prohibited within 20 FEET of any oxygen cylinders, including FDNY vehicles and ambulances equipped with oxygen

Ogura Cordless Rebar Cutter: A: The Ogura cordless rebar cutter is designed for cutting maximum 1" diameter high tensile rebar, tensile fastening bolts, locks and threaded rod. B: The support handle CAN BE INSTALLED EITHER ON THE LEFT, RIGHT AND TOP SIDE of the cutting head C: Do not start cutting immediately after the motor is switched on. Allow the Tipped Saw blade to reach full speed before beginning to cut. D: The tool has "high speed mode" and "high torque mode". The mode indicator, located on the handle, will light up when the tool is in "HIGH TORQUE MODE" TB Tools 28 Data Sheet 2: 3.1, 3.4, 3.6, 4.5

Still Water Operation: A:There will be NO MOTORS NO OARS issued with the boat as the intent is for members to slowly row stranded people to safety in water moving less than one knot B:The maximum capacity of a flat bottom boat used in still water operations is 3 C: No member shall enter enter the water unless equipped with a Cold Water Suit or waders and a personal flotation device (PDF) D: A Water Rescue Company consists of a Water Rescue Company and an Engine Company. When the Water Rescue Company is an Engine Company then a neighboring Engine Company will be dispatched to assist in operations STILL WATER "Water rising, but non-flowing, flood waters"

LADDERS 1 - ALUMINUM LADDERS They will dent but will not chip or crack when subjected to severe impact, nor will they fail suddenly because of overloads. They will bend but not break, as wood does. No protective finish is required on aluminum ladders, as they will not dry out and weather with age or sunlight exposure. A slow oxidizing of the surface occurs, but it can be polished off.

TL The 1 ½" TIP is preferable when deep penetration of the stream is necessary to hydraulically overhaul stock. Increasing nozzle pressure within allowable limits will often facilitate access into partitions and sidewalls. The application of a LCS downward into roof openings from an elevated position can be counterproductive. Operating the Tower Ladder stream into roof vent holes is generally ineffective and may result in a prolonged operation.

A Lieutenant who would like to submit information about an incident into the "Pass It On Program" should email the information through the chain of command to the Bureau of ___________________ within ____________ hours of the operation. Operations/ 24 NOT THE B OF SAFETY OR TRAINING 2 COPIES SENT TO UNITS: ONE PLACED ON BULLETIN BOARD WHERE CO DRILLS ARE CONDUCTED OTHER IN BINDER IN CO OFFICE SB 6

TL The stokes basket may be lashed to a substantial part of the bucket in an upright, horizontal or diagonal position, with the DIAGONAL position preferred as it is the easiest and safest option., at least 25'-30' from the building

IED If first unit on scene, confirm the location of the POI USING PLAIN LANGUAGE on the department radio. Notify the dispatcher and advise incoming units that an explosion has occurred, so that all incoming units may alter response routes when necessary. Consider staging in a protected area, being mindful of distance and/or shielding. ERP add 3 sec 5.3.4

TRENCHING A) A trench may be cut, BUT SHOULD NOT BE OPENED, until there is an adequate vent opening directly over the fire. Ideally, the trench should be precut, but not pulled B: TWO OR MORE INSPECTION HOLES may be cut on the fire side of the trench. When, and if, the fire reaches the inspection holes, the precut trench is pulled. C: The trench must be properly located, AT LEAST 3' wide, and cut from wall to wall or other suitable fire stop, such as a stair or elevator bulkhead. D: The trench should be cut about 20 FEET from the initial vent hole. It should be cut at the narrowest, available roof section, taking advantage of bulkhead structures, outside walls, skylights, etc. Note: Do NOT depend on firewalls constructed within the structure. MD Ch 1 4.9.9 B, C, E

Members entering the Rehabilitation and Care area should normally rest for approximately how many minutes before being reassigned? 20 MINUTES AUC 230 sec 7 If a unit is assigned to Rehabilitation, then all members from that unit must take part in medical monitoring...sec 7.11 Members will be considered patients if: - They are complaining of illness or injury - Have symptoms of CO exposure or hypoxia - Have a SpCO of 15% or greater- Have a SpO2 of less than 90%

The Kernmantle life-saving rope (KLSR) shall only be used for life saving purposes. The KLSR must be placed out of service in all of the following situations: A: It comes in contact with acid fumes. B: It's subject to an impact load. C:It's subject to the weight of TWO personS D: It's frozen. "Deputy Tony Hit An Inside Fastball Away" Doubt Two people Heat Acid/fumes Impact load Frozen Abrasion *THE REGULAR LSR HAS TWO ADDITIONAL SITUATIONS THAT REQUIRE IT TO BE PLACED OOS THAT ARE NOT MENTIONED FOR THE KLSR: HOCKLE (40-50% LOSS) AND PERSISTENT RUST* TB Rope 10 4.0

You have just been hired to staff E-522 the Reserve Apparatus in E-329's quarters. As a Lieutenant in charge of this apparatus: C:During the tour, you utilized the battalion depot for any OOS CFR equipment D: E-522's officer will be responsible for filling out and forwarding a Lost Property Report upon the discovery any equipment lost after deactivation of E-522 The officer who was in charge of the apparatus while it was out of storage is responsible for the preparation and forwarding of the Lost Property Report Explanation:AUC 259

The SENSIT gas detector will detect a gas source as low as ____ ppm. 20

Wind impacted fires in fireproof multiple dwellings can present many challenges to operating members A: Experience has shown that conditions at a wind impacted fire in a fireproof multiple dwelling will severely tax the resources of the 2ND TO ARRIVE LADDER COMPANY KO CURTAIN would normally be the first tactic used due to its availability and time it takes to deploy. Note: Firefighters from the 3rd to arrive ladder, rescue or squad company, equipped with forcible entry tools, may be assigned to force entry into the apartment below the fire apartment in order to secure the ropes of the WCD and/or provide access for the HRN engine company. MD Ch 5 4.2.1 C, 4.3.1 D, F, 5.1.4

There are many things to take into account when positioning a tower ladder bucket for large caliber stream (LCS) operations: A: The bucket should be positioned outside the vertical collapse zone while maintaining an effective stream. When collapse is feared, the height of the wall vertically above the bucket is the minimum distance horizontally that the bucket should be away from the wall. B: The member operating the joystick in the bucket should pre-plan bucket movement in the event of an imminent or actual collapse. **When operating at UPPER FLOORS, this will generally be UPWARDS **When operating NEAR THE EDGE OF THE BUILDING, this will generally be TO ONE SIDE This provides an extra pair of eyes to warn of impending danger and override bucket controls in an emergency. The Pedestal Firefighter must don PPE and be continuously aware of changing fire conditions. This member should have a working knowledge of the location of other operating units. C: Whenever a Tower Ladder LCS operation is in progress, the pedestal position shall be staffed. D: The member on the PEDESTAL should consider activating the platform control switch and/or Safety Interlock Foot Pedal DURING OVERHAUL and whenever MEMBERS OR CIVILIANS ENTER OR LEAVE an elevated bucket to prevent accidental movement. TL Ch 4 4.3

On the EV 6000 thermal imaging camera, when colors yellow through red appear in more than _______ % of the display, it will shift into ______ sensitivity mode. 32, LOW SENSITIVITY MODE NOTE: LOW SENSITIVITY IS WHEN IT IS HOTTER BE AWARE WHEN IN "LOW" HEAT MODE THE CAMERA IS IN "HIGH" SENSITIVITY MODE. WHEN IN "HIGH" HEAT MODE THE CAMERA IS IN "LOW" SENSITIVITY MODE.* *BE CAREFUL WITH THIS TERMINOLOGY *TB Tools 27 Data Sheet 1 3.4.7, 3.4.8

There are times when members of a Tower Ladder may be working during extreme cold or icy conditions: A: Use rock salt or speedy-dry on icy surfaces under and around jack and outrigger pads to prevent slipping. B: During operations in freezing weather, frequent boom repositioning will prevent ice buildup. However, if operations are to remain stationary, the boom should be periodically EXTENDED AND RETRACTED to prevent ice buildup. C: During extreme cold weather the TOWER LADDER OFFICER should facilitate periodic relief of members in the bucket to prevent overexposure to the elements. D: During winter storms, the VEHICLE RECOVERY STRAP attached to a Tower Ladder may assist in vehicle/apparatus/ambulance recovery **(NOT A cable or chain attached to a Tower Ladder) Notes: Units engaged in outside operations shall keep the apparatus engines running to prevent congealing of diesel oil. During extended operations, consider placing all pressurized water extinguishers in the crew cab. During periods of heavy snow accumulation, Tower Ladder units should be guided by the following: When conditions warrant, Department-issued snow chains shall be mounted on all four outer drive-wheel tires Prior to setting jacks/outriggers on surfaces, clear snow to verify stabilizers are not being lowered onto manholes/vaults. TL Ch 5 6

All members assigned to an aerial ladder company should have an understanding of Department policy on aerial ladder training, use and maintenance: A: Chauffeurs should be familiar with the operation of all other aerial ladders; engine company chauffeurs should be familiar with the AERIAL LAD OPS of ladder companies that they respond with on 1ST ALARMS. B: When right angle positioning is prevented by other apparatus or parked vehicles which cannot be easily moved, an angled extension over the cab or trailer may be necessary. C: If fire is in an "H" or "U" type building and conditions do not mandate a specific position, avoid blocking the front entrance to the courtyard when it is apparent that a tower ladder may operate at that location. D: Vacant lots or driveways adjoining the fire building MAY ALLOW for BETTER placement of the apparatus when overhead obstructions might interfere with operations Lad 2 7.1.7 - 7.1.9

UNDER RIVER RAILS C: Treat these incidents as CONFINED SPACE OPS and take precautions accordingly. D: Once committed to the tubes, members must realize that the route they approached from may be their only means of egress. Conditions at the scene may not allow members to pass to the other side of the inciden

When placing the aerial ladder to the roof of a building, extend the ladder so that the tip is? At least 5 feet above the POINT WHERE THE LADDER COMES IN CONTACT WITH THE BUILDING

UTAC channels: A:The primary channel to be used with cooperating agencies in the NY region is Zone B, Channel 9, UTAC 42D. B: The secondary IO channel to be used when there are multiple operations in progress and the primary channel is unavailable is 41D. THIRD IS 43D C: UTAC repeater channels are only intended for EXTERIOR OPS, CAN NOT BE RELIED UPON FOR INTERIOR OPS D: When transmitting on a REPEATER CHANNEL, members must press and hold the push to talk button for 2 SECONDS before beginning to speak to allow the repeater to activate and not cut off the beginning of the message. Which of the following would be most correct when choosing the primary utac channel for an incident involving NJ FD: UTAC 2T/A COMMUNICATIONS MANUAL - CHAPTER 14 - ADDENDUM 4

f fire appears behind the nozzle team as they are advancing the hoseline, it must be immediately addressed. This problem can be complicated if the nozzle team is operating in a narrow area that would prevent the nozzle firefighter from simply turning around to extinguish the fire behind them: A: The nozzle firefighter should bend the hoseline back on itself and pass the line to the back-up firefighter, who is better positioned to extinguish the fire behind them. The nozzle firefighter will act as their back-up while they operate the hoseline. B: When passing the nozzle back, the nozzle firefighter should be sure to turn towards the hoseline to avoid getting tangled in the line. C: The nozzle will PASS OVERHEAD as it is bent back and SHOULD BE MAINTAINED OPEN, IF POSSIBLE D: Once the fire behind the nozzle team is extinguished, the back-up firefighter will similarly bend the line back in the original direction and pass the nozzle back to the nozzle firefighter to continue advancing the line. Eng Ch 6 2.7.18

VACANTS A Tower Ladder should be placed in front of the fire building because of the increased likelihood of an exterior attack. Also, it may be desirable to place an Engine Company in close proximity to the building, outside of the collapse zone, in order to operate the deckpipe for an exterior attack.

At a 2nd floor fire in a 4-story Brownstone, the first arriving Ladder Company brought in a number of tools: A: The Extinguisher Firefighter brought the 6' hook, pressurized water extinguisher, Flashlight and HT. B:The Forcible Entry Firefighter brought the Maul, Halligan, rabbit tool, Flashlight and HT. C: The OV Firefighter brought the 6' hook, Halligan, Flashlight and HT. D) The Roof Firefighter brought the HALLIGAN, 6' Halligan Hook, Flashlight, HT and Life Saving Rope (LSR) B Note: Instead of the Maul, this member could have brought the Axe C Note: For top floor fires, the saw is taken in place of the hook. BS/RF 2.6

VENT PROFILE A: In addition to evaluating the smoke venting from the building, it is equally important to evaluate the air being pulled into the building which is an indicator of a ventilation-limited fire condition. C: On arrival, a vented fire should not be considered a favorable condition; we must still control, communicate and coordinate ventilation tactics. D: While in the DECAY STAGE, the fire may no longer have enough pressure to push smoke from the fire area or building. The assumption that the absence of smoke pushing from a building is a positive sign is not accurate.

Which of the following choices is CORRECT regarding Emergency Roll Calls? A: The Bureau of Operations mandates training roll calls to be conducted QUARTERLY. Incident Commanders are encouraged to conduct training emergency roll calls whenever they feel it is warranted. B: Training roll calls will be conducted Upon the completion of operations (not during fire operations) C: Chief officers should use this time to have company officers conduct the training roll calls as a way to prepare for an actual occurrence. D: Rescue company members shall answer the roll call as per ladder company position assignments. Squad companies answer according to Engine company position assignments COMMUNICATIONS MANUAL - CHAPTER 9 - ADDENDUM 2 - EMERGENCY ROLL CALL PROCEDURES

VENTILATION Vertical ventilation methods of releasing smoke and heat from inside the fire building will generally create UNIDIRECTIONAL flow paths.

Engine Companies have a variety of tools that help members complete their assigned mission on the fireground: A:The ANALOG IN-LINE PRESSURE GAUGE (OLD SCHOOL ONE) is used to monitor PRESSURE being delivered from the standpipe outlet. Like the digital in-line gauge, IT DOES NOT REGULATE WATERFLOW; it simply monitors the pressure of the water supplied. Unlike the digital in-line gauge, the analog gauge DOES NOT measure water FLOW. B: The FOAM NOZZLE can be identified by WHITE MARKINGS ON THE TIP, handle, and pistol grip. When supplied with 200 psi, it has a flow of 125 GPM. C:The MULTIVERSAL has two 3" inlets. The maximum pressure to be supplied to the appliance base is 200 psi. D: The Bresnan distributor is supplied with a 2 ½" hose. A shut-off should be placed one length from the distributor. Eng Ch 3 6.2.1, 7.2, 7.3, 8.3, 10.4, 10.5

Ventilation at nonfireproof multiple dwelling fires must be carefully conducted: A: Windows directly exposed to fire across shafts or directly over the fire should not be opened until the exposing fire is controlled either by partial or complete extinguishment or by having a charged hand line at these extension points. B: When using a fire escape for access to different floors, never vent a window that could allow fire to cut off the line of retreat. C: When venting the windows of the fire apartment from directly above by use of a 6` hook and an intense fire is suspected, the possibility of fire rolling up the side of the building when air is admitted must be considered. For safety, look down at the window to be removed, measure the distance with the tool, pull your head back in the window and then swing the tool through the window below. D: When venting the windows of the fire apartment from the fire escape first check them for heat. See if they show cracks from the heat and look for discoloration of the glass (GENERALLY BROWNISH) from the heat. If above observations indicate extreme heat, the fire may momentarily vent itself or light up as you ventilate. NOTE: EEWs may not give any of these indications; contact Ladder Company Officer before VEIS. Lad 3 5.7.4-5.8.2

AUC 277 HOLDING AREAS Window sills on windows providing access to the holding area shall be painted red, inside and outside, with a sign attached outside on TOP OF WINDOW PANE. This sign shall read "F.D. ACCESS" (Red lettering on a WHITE background)

When a 5 firefighter Engine company is reduced to 4 firefighters after the start of the tour, the company officer shall tell the dispatcher enroute to an alarm: In this situation respond without telling the dispatcher anything Explanation:- Ladder, Rescue, or Squad Companies responding with 4 firefighters will tell the dispatcher enroute "We are responding with 4 firefighters" - Any unit responding with less than 4 firefighters will tell the dispatcher enroute "We are responding understaffed" 5 firefighter engines reduced to 4 firefighters after the start of the tour will respond as normal AUC 287 sec 8.2

Marine companies carry 12 foot and 20 foot portable hook ladders with wood beams: A: They are painted BLACK except for the hooks and for 18 inches at the base of each beam, which are painted WHITE B: The length of the ladder and company identification is stenciled on the exterior of both beams. C: The hooks, unlike those on roof or hook ladders carried by land units, are fixed. D: These ladders do not have metal spurs at the base; there are simply the squared edges of the wood beams. Lad 1 1.2

When a Metrocard is lost, stolen, or damaged the officer on duty shall immediately notify the FDNY RESOURCE CENTER

During company drill, members were discussing ladder company tactics at cast iron and mill loft buildings: A: Large, open floor areas require all ladder companies carry search ropes and thermal imaging cameras. B: Fire-vented windows where wind is blowing the fire back into the fire occupancy may require the deployment of KO curtain(s) and/or the fire window blanket. C: When sprinklers are manually shutdown, a member should remain at the shut-off valve in case the system needs to be reactivated.. D: Indiscriminate overhauling on the uUNDERSIDE of segmental arch floors can cause a localized collapse. Lofts 7.1.7, 7.1.12, 7.1.16, 7.1.17, 7.1.19

When arriving to a fire in a Con-Ed electric substation: A: Units shall report to the designated muster site B: Have a Con-Ed white hat retrieve information from the Lockbox located INSIDE the substation. The Lockbox contains info that can be useful to the IC including PCB info, overhead photo, a site diagram and list of the hazards present at the substation C: If a Con-Ed representative (White hat) is not on scene then call the posted number and request one to respond D:If a sprinkler siamese is present, stretch a 3 1/2" supply line to the siamese. Only charge the supply line if requested by Con-Ed white hat AUC 338 add 2 sec 4 and 5

Ladder 177 had an interesting tour with several out of the ordinary responses. IN ALL OF THESE EXAMPLES, SIGNAL 10-43 SHOULD BE THE SIGNAL TRANSMITTED A: Following a response where the members removed a worker stuck on top of an elevator car, B: Following a response where the members used a rescue swimmer to remove a victim from the water 10-46 CODE 2-- It is transmitted for Marine personnel removing persons from the water. C: Following a response where the members operated at a man under in the subway D:Following a response where the members operated at an off level occupied swinging scaffold.

When encountering an emotionally disturbed person (EDP): A: No attempts to forcibly restrain an EDP unless there is direct threat of physical harm to members of the department B: Transmit a 10-47 and state "Possible EDP" C: Where EDPs are threatening to jump from a window ledge, bridge, etc., the primary concern shall be for the safety of persons using sidewalks, and roadways below D:If there are no indications of fire, or other imminent danger, members will not attempt to force entry into an apartment. Instead members will wait for the arrival of NYPD and force entry only at the request of the NYPD AUC 271

You are trying to remember what to bring to the Incident Command Post upon arrival as a Ventilation Support Group Company. 27" Tempest PPF and exhaust hoses- Eye and ear protection- Dave Clark headset- CO monitors- Elevator keys- Halligan and HEAVY AXE- Door chocks- Handlights- SCBA and full PPE AUC 349 sec 4.1 NOTE: NO SEARCH ROPE

When locating a member in distress our main concern is the timely removal of the member from the IDLH. A: If the member is unconscious or unable to assist in their own removal, the member(s) who FIRST FOUND THE FF must start the packaging process.

Regarding the transmission of the 1045 signal: A: Other than to address any patient discrepancies, the 10-45 shall not be cancelled once it is transmitted B: Signal 10-45 code 3 and 4 DO NOT require the submission of a BF 19 form. C: Signal 10-37 with any code shall not be used at any fire operation. D: Signal 10-45 shall not be used to indicate a fatality or injury to an on-duty member.

When operating in a Ventilation Ladder company, there are designated titles that should be used when operating at an incident: A: The UNIT assigned to respond with the Positive Pressure Fans (PPF) shall be designated the "Ventilation Support Group" B:The OFFICER shall be designated as the VENT GROUP SUPERVISOR C: The members assigned to OPERATE THE FANS shall be designated "Vent Group Lobby Unit" and the "Vent Group Fire Unit" D: The member assigned the roof shall be designated VENT GROUP ROOF AUC 349 sec 6.1

SCBA Pak-alert alarm system: A: The full alarm condition can only be cleared by manually pressing the RESET BUTTON TWICE, located on the side of the control console. B:The pre-alarm condition can be reset by pressing and holding the reset button until 3 quick audible chirps are heard and the red flashing light on the control console is replaced by a green flashing light NOT BY SHAKING THE CONTROL CONSOLE. SHAKING THE CONTROL CONSOLE WILL NOT RESET THE PAK-ALERT. THE MOTION SENSOR IS IN THE SENSOR MODULE UNDER THE AIR CYLINDER VALVE AND NOT IN THE CONTROL CONSOLE, SO THAT ACTUAL MOVEMENT OF THE SCBA BACKFRAME IS REQUIRED FOR RESET. C: If the sensor module does not sense motion of the SCBA for 20 seconds, the Pak-alert will signal a pre-alarm condition. If there is still no motion for the next 12 seconds, the full alarm will sound. D: Provided working batteries are in the Pak-alert, the manual alarm may be activated by pressing the manual alarm button at any time, even when the SCBA is not pressurized. SCBA 3.10.5, 3.10.6 C & D 3.10.7 B, 3.10.8 B

When operating the power saw if the guide man slaps the operator two times on the back, the operator should be aware that this means he/she should do what? STOP CUT ONE SLAP = STOP (ONE WORD) TWO SLAPS = START CUT (TWO WORDS) THREE SLAPS = SHUT DOWN SAW (THREE WORDS) TB Tools 9 4.4.6

CLASS 2 Occasionally, the building will be divided into wings or sections above the first floor with each section having their own standpipe, stair(s) and elevator(s). In most of these buildings, the only location where members may traverse from one section to another is the lobby, cellar and/or roof. C: The "Service Stairs" will be of standard width, rise and run. It usually contains a standpipe, service elevator and door(s) to the apartment(s) that are typically not the main entrance to the apartment(s). D: "Open Fire Stairs" are the most common fire stair encountered and generally have two doors serving separate apartments in a building or wing of a building, though some contain only one door serving a single apartment. Open fire stairs may be found anywhere in the apartment and typically DO NOT have a STANDPIPE

When performing overhaul operations, all members must wear their Department issued PPE INCLUDING bunker coat, bunker pants, bunker boots, helmets, protective hoods and gloves.

TAC U channel: ****TAC- U ZONE B -Channel 12 U- TAC ZONE B CH 9 Channel 42D B: 5 watts. C: Emergency alert tones are only audible on the channel on which the emergency alert has been activated. D: If an emergency alert tone is activated on this channel, the on-scene ranking POLICE OFFICER must be informed that an emergency alert tone has been activated. COMMUNICATIONS MANUAL - CHAPTER 14 ADDENDUM 2D

When refilling and pressurizing the water extinguisher members must take proper safety precautions: A: Always ensure all pressure is properly relieved from the extinguisher prior to attempting recharge. B: Regulated extinguisher pressurization source should never be set higher than 125 PSI. C: NEVER stand directly in front of the extinguisher gauge or stand over the valve during pressurization. D: THE APPARATUS HAS A ONE WAY VALVE IN THE AIRLINE TO PREVENT WATER FROM ENTERING THE BRAKE SYSTEM TB Tools 1 6.0

Be able to "read" smoke is a carefully acquired skill: A: The volume of smoke may indicate the size, location and stage of the fire within a structure. Note: However, the volume of smoke may not always be visible and can be concealed by various building configurations. B: Smoke velocity is an indicator of pressure that has built up within a structure. Note: The pressure is developed by buoyancy and expansion due to the amount of heat released by the fire. C: Turbulent Smoke indicates extreme heat (closer to the fire). Note: Smoke flow can be either laminar (smooth) or turbulent based on the velocity and temperature. Cooler smoke appears to flow smoother. Hotter smoke will appear to boil and move quickly upwards in a turbulent fashion. TB FD Ch 2 3.5.1, 3.5.2

When relocated to another quarters near the change of tours you must notify the dispatcher that relief will or may be required. This notification shall be made at: 0800 or 1700 hours Explanation:AUC 217 sec 4.1

The A-8 Fire Department Referral Report shall be used for the referral of non-serious conditions that require a follow up evaluation by the Bureau of Fire Prevention or the Bureau of Public Transportation Safety Unit (PTSU): A: Conditions found that require both a Fire Prevention referral and a PTSU referral MUST BE ON SERPERATE REFERRALS B: If upon inspection of a city owned or operated facility, an A-8 is forwarded for a condition that a city agency has jurisdiction over, by placing an "X" in the CITY AGENCY box in the UPPER RIGHT HAND CORNER of the A-8 C: Inspection and enforcement procedures in leased commercial spaces ON TRANSIT AUTHORITY PROPERTY should proceed in the same manner as if the space was NOT on Transit Authority. If an A-8 is being forwarded for a condition that is the concern of the Fire Department, it shall be forwarded to Fire Prevention D: Each A-8 is sub-divided into TWO CATAGORIES, Fire Prevention referrals, and PTSU referrals AUC 5 ch 3 add 4

When using the Pak-Tacker to track a missing member: A: To begin searching, the Pak-Tracker should be held at WAIST HEIGHT out in front of the operating member - the top of the hand-held receiver should be pointed toward the target B:When the signal strength rises above the 50-percent level, the row of LEDs will begin to light starting with RED at the bottom, YELLOW in the middle, and GREEN AT THE TOP NOTE: THIS IS OPPOSITE A TRAFFIC LIGHT C: Use the Pak-Tracker in a sweeping motion, very slowly in a horizontal direction first. D: Always, move toward the highest relative signal strength. SCBA Addendum 8 7.6, 7.8, 7.9

Members of Ladder 300 in Staten Island were reviewing characteristics of lightweight constructed private dwellings: A: When lightweight components are exposed to fire or high heat, the IC shall be immediately notified. B:It is MANDATED that the eCIDS program be utilized to identify buildings of lightweight construction so that units are notified prior to arrival. C: Areas unsupported by columns with spans greater than 25' are generally an indication that lightweight construction is present. D: In ANY BUILDING CONSTRUCTION, the critical area subject to failure as a result of fire is the POINT OF CONNECTION. PD Ch 6 1.5, 1.8, 1.10, 1.11

Which of the following choices is CORRECT regarding company member and officer actions during an Emergency Roll Call: A:When answering the roll call, all company officers will state the number of firefighters RIDING ON THE APPARATUS & account only for members within sight or hearing without using the HT B: The Company Officer will account for their members under IMM SUPERVISION The Roll Call officer will contact the remaining members of the company C: If a member's involvement in a rescue is necessary and they are unable to complete their assignment, they must notify the INCIDENT COMMANDER D: Members in the NOT IN THE IMM VICINITY of a member in distress must refrain from self deploying and becoming involved in any rescue effort unless specifically ordered COMMUNICATIONS MANUAL CHAPTER 9 - ADDENDUM 2

During a severe storm, units should not be committed to dewatering operations. The FDNY makes 4 exceptions to this policy: A: Where failure to dewater creates a serious fire hazard, such as; flood or rising water in close proximity to live electrical equipment or service, which cannot be disconnected safely B: Where lives are endangered, such as, but not limited to; hospitals, nursing homes, and similar type of occupancies C: Where extensive property damage can be averted D: A flooded depression in the roadway on the Long Island Expressway, such as, the roadway under an overpass creating a dangerous traffic problem AUC 159 add 9 sec 2.3

Which of the following responses to a verbal alarm while assigned to another response: A: In the event the unit is responding to another alarm, and it is EVIDENT human life is NOT in jeopardy at the scene of the verbal alarm, the unit shall proceed to the original alarm after transmitting radio notification of a verbal alarm to dispatcher and receiving acknowledgement. NOT THIS: While enroute to an electrical emergency, Engine 223 is flagged down on a verbal for a large rubbish fire that is extending to an unoccupied car. The officer advises the dispatcher of the verbal and stops to extinguish the extending fire. B: While enroute to a first due gas leak, Engine 244 is flagged down on a verbal for a civilian hit by a bus. The officer advises the dispatcher of the verbal and stops to provide medical care to the injured civilian. C:While enroute as the extra engine to a fire in an MD with reported people trapped, Engine 256 is flagged down on a verbal for fire coming from the windows of a PD. The officer advises the dispatcher of the verbal and stops to operate at the second structural fire. Until the unit stops to assess, it is unknown whether human life is in jeopardy D: While enroute to a difficulty breathing CFR response, Engine 269 is flagged down on a verbal for fire coming from the windows of an isolated vacant building where there is no life hazard. The officer advises the dispatcher of the verbal and continues onto the CFR response. There is no life hazard. The unit is required to proceed to the original alarm **COMMUNICATIONS MANUAL - CHAPTER 6 - ALARM RESPONSE**

Two members of Engine 300 were discussing the common features of private dwellings: A: Two entrances are most common; the main entrance is usually located in the front, but sometimes is located on the side as seen from the street. B: Secondary entrances can be located on the front, side and/or rear. *C: In STRUCTURES MORE THAN ONE STORY, the INTERIOR STAIRS TO THE CELLAR will usually be located UNDER THE MAIN STAIR. Note: Throughout the city there have been many renovations to private dwellings. As part of these renovations, the interior stairway may have been moved or sealed off. It is common to find a closet in the area where the stairs were once located. D: With SEMI-ATTACHED STRUCTURES, or those with MIN SPACE ON ONE SIDE, the INSIDE CELLAR STAIR will usually be found NEAR THE SIDE OR REAR ENTRANCE PD Ch 1 2.4

Which statement in regards to Satellite Units: A: Satellite Units carry Hi-Ex Foam generators B: Satellite Units carry an ample supply of five-gallon cans of Hi-Ex Foam concentrate C: Satellite Units carry a Modified Angus Foam Cannon that may be mounted on a Satellite deluge gun or a Tower Ladder D: Only when a Satellite Unit ENTERS OR LEAVES QUARTERS, ONE MEMBER shall be assigned and positioned to make sure that the deluge gun is placed so that it clears the doorframe AUC 274 sec 5.6, 5.7, and 7.1

The Post Radio was developed to assist with field communication issues in a variety of buildings and structures around the city. A: Power output of 45 watts supplied by a rechargeable 12-volt, 18 amp/hour sealed lead acid battery. B: Using the 20% transmit, 20% receive, 60% standby formula, the battery provides sufficient wattage for 4 hours of operation. 10/10/80 = 7 HOURS C:The battery shall be charged weekly and after each use for at least 8 hours. D: Prolonged use may require up to 20 hours to fully charge. COMMUNICATIONS MANUAL - CHAPTER 12 - POST RADIO

While conducting a drill on roof operations, a member of ladder 171 dropped his radio causing excessive damage and rendering the radio inoperable. A spare was requested by the officer on duty while members discussed the spare radio procedure A: Immediately notify the administrative DIVISION for the need for a spare radio. B: Forward defective radio with battery, antenna, and remote speaker mic to Division NO CASE C: Upon receipt of the spare radio, Ensure proper ID has been placed in HT by transmitting from SPARE HT TO ANOTHER HT (Not the other way around). D:An Unusual Occurrence Report is required for excessive damage to the radio. Explanation:COMMUNICATIONS MANUAL - CHAPTER 11 ADDENDUM 4

FIRE DYNAMICS D: Backdraft Indicators include no visible/active flaming within the compartment and extremely limited or no ventilation of the fire compartment. C) A backdraft MAY lead to a heavy fire condition OR may expel all of the fire gases, leaving ONLY LOCALIZED COMBUSTION in its path.

Word of a complicated fire which resulted in fatalities quickly circulated through the department and the members of Engine 256 and Ladder 177 which did not respond were interested in getting the Battalion recordings: A: Unusual to request recordings for an incident at which an officer's unit did not operate. Any such request considered by Operations and only granted if there are valid reasons justifying such request. B: Company Officers can request the PRIMARY AND SECONDARY TACTICAL CHANNELS. CAN NOT REQUEST COMMAND CHANNELS C: Incidents involving serious injuries, fatalities, and high profile incidents will be made available only at the discretion of the Chief of OPERATIONS D: Officers or units requesting HT audio must send an email from an FDNY email address to the HT recorder unit. COMMUNICATIONS CHAPTER 9 ADD 1 SECTION 8

While conducting a drill on portable ladder placement at tenements and multiple dwellings with rear fire escapes: A: Overcrowding on the fire escape in the rear may be relieved by members assisting occupants to the roof via the GOOSENECK ladder. B: In the event of a fire in a building with rear party wall balconies, where fire has spread to the adjoining building, occupants may be trapped on the balconies. A 12' HOOK LADDER may be used to gain access to the various balcony levels by the Roof or OV firefighters for search and rescue. C: Portable ladders must, if possible, be taken through the 1st floor public hall, apartments or store to the rear yard to effect rescue. D Note: It can also be taken through the 1st floor public hall, apartments or store to the rear yard D: The 12' hook ladder may be brought to the roof via Aerial, Tower Ladder or utility rope and lowered to the top balcony. Lad 1 10.1

Your Ladder Company is enroute to a 10-76 4th alarm with heavy fire on two floors of a high rise office building. The Lobby Control Unit is in place and both a Staging Area and Forward Staging Area are established. Where should your unit report when 10-84? THE STAGING AREA Greater alarm or special called ladder companies after the fourth arriving ladder company shall report to the ICP in the lobby or if staffed, the Lobby Control Unit. UPON ESTAB. OF A STAGING AREA OUTSIDE the building, units will report into the Staging Area. HROB 8.7

Tank truck accident with a fire: A: With the older steel tanks a BLEVE can occur. B: When the chance of a BLEVE exists it is extremely important to get a large caliber stream on the vapor area of the tank quickly. C: With the newer aluminum tanks, the problem of a BLEVE has been REDUCED BECAUSE THE SHELL WILL MELT AT APPROXIMATELY 1220 DEGREES F. D: If enough resources are on scene, members shall stretch a foam handline in conjunction with the operation of a large caliber stream.

dvancing a hoseline under certain conditions can be challenging for Engine Company members. A: When advancing a hoseline down a flight of stairs the nozzle firefighter should keep one leg out in front to check for the presence and integrity of each step as he/she descends. Leaning back against a wall can help guide the descent. B: When advancing a hoseline down a flight of stairs, if high heat is present, the nozzle firefighter should keep the nozzle OPEN during the descent and LIFTED UPWARDS to cool the stairway while descending C: In the event the advance of a hoseline is stalled due to insufficient available hose, the back-up firefighter may need to momentarily leave the nozzle firefighter to retrieve the hose necessary to continue the fire attack. This must be coordinated with the officer and nozzle firefighter. D: In larger apartments or private homes, the door firefighter may be forced to move into the fire area to keep line of sight with the nozzle team. Maintaining VISUAL contact with the nozzle team is necessary. Eng Ch 6 2.7.17 C, D, 3.10, 4.5.5


Related study sets

Evolutionary Psychology OU Chapter 6 (Altruism)

View Set

2.2.6 OSI Model and Data Encapsulation

View Set