EA 160 Review chapter 5

¡Supera tus tareas y exámenes ahora con Quizwiz!

How many receptacles are required for 90 linear feet of show window area?

8

The load for 6' of multi-outlet assembly used simultaneously is...

1,080VA

The general lighting load (expressed as a unit load per square foot) for a warehouse is...

1/4VA/ft squared

What is the calculated load, in amps, for a 120V circuit supplying four 150W recessed incandescent fixtures and six recessed fluorescent fixtures operating continuously? (Each fluorescent ballast is rated at 0.65A.)

11.125A

Branch circuit conductors supplying continuous duty loads are calculated at

125% of the rated load

What is the maximum number of general purpose non-continuous duty duplex receptacles that can be connected to a 20A, 120V circuit in a commercial building? What is the NEC@ required load rating for each receptacle?

13 receptacles; 180VA

What is the capacity, in amperes for a 20A circuit breaker supplying a continuous load?

16 A

What is the minimum conductor ampacity for four 1,000W, 208V, 1Ø electric baseboard heaters?

19.23A

What is the Current-carrying ampacity for each of 10 No. 10 THHN copper conductors installed in a single conduit?

20 A

A continuous load is defined by the NEC as a load whose maximum current is expected to continue for at least...

3 hours

What is the total load, in VA, for two small appliance branch circuits in a single-family dwelling?

3,OOOVA

Using the resistance formula, the voltage drop for an 18A, 208V, 3Ø load with a total circuit length of 105' using No. 10 solid copper conductors is...

3.96V

The General lighting load for a store is...

3VA/ft squared

What is the demand load, in amps, for one household electric range with a nameplate rating of 16.75kW, 1phz 240V?

41.67A

What is the demand load, in amps, for a single circuit supplying one wall-mounted oven rated 11.75kW, 1Ø, 240V, and a countertop cooking unit rated 9.6kW, 1Ø, 240V?

48.33 A

The voltage drop between the point of service and the farthest outlet in a branch circuit should not exceed...

5%

The voltage drop for a 480V, 3Ø circuit with a load of 26.5A, using No. 8 stranded copper conductors at a circuit length of 145' is...

5.18V

The voltage drop for a 208V, 1Ø circuit with a load of 26.5A, using No. 8 stranded copper conductors at a circuit length of 145' is...

5.98V

Which size copper branch circuit conductors are required to supply an air conditioning unit with a nameplate rating of 33.5A, 208V, 3phz

No. 6

Load calculations for circuits supplying lighting units with ballasts are based upon...

the ampere ratings of the ballasts


Conjuntos de estudio relacionados

Lecture 5: Climate variability (ENSO)

View Set

BIM 1 Mid-Term Review #2 (Office Basics + Word)

View Set

Anatomy and Physiology Ch. 4 (Exam 2)

View Set

AU 60 - Assignment 1 - Fundamentals of Underwriting

View Set

Life Insurance and Annuities-Policy Replacement and Cancellation

View Set

ACCTCY 4356 - Exam I Question Bank

View Set

KPLAN - 3 of 3 - Q & A - Structural Systems

View Set

Series 66 Unit 2 Checkpoint Exam

View Set

Physical Science for Educators Final

View Set

COMSC-210 Midterm Exam Practice Test, COMSC-210 Quiz: AVL Trees, COMSC-210 Quiz: Hash Tables

View Set