g3

¡Supera tus tareas y exámenes ahora con Quizwiz!

What is the minimum-size copper equipment grounding conductor required for a 60-ampere branch circuit?

10 AWG

NEC Table ? is required to be used for minimum sizing of equipment grounding conductors for branch circuits and feeders.

250.122

What is the circular mil area of a 6 AWG copper conductor?

26,240

Equipment grounding conductors installed with medium-voltage cables are generally required to be sized based on Table 250.122 and never smaller than ? copper.

6 AWG

The NEC is made up of an introduction and ? chapters.

9

Which of the following does not contain mandatory requirements in the NEC?

Annexes

According to the NEC Style Manual, if a term is used in more than two articles, it qualifies for inclusion in ? .

Article 100

If a grounding and bonding word or term appears in more than two NEC articles, it qualifies for placement in ? .

Article 100

A main bonding jumper is the connection between the grounded conductor and the equipment grounding conductor and is located at a separately derived system.

False

A supply side bonding jumper is required to be sized based on the overcurrent device protecting the circuit.

False

Chapter 8 in the NEC is independent of the other articles, and none of the rules in the rest of the NEC applies to communications systems.

False

Informational notes in the NEC are applicable as rules and must be applied to the rule they follow.

False

When grounding is accomplished through a resistor, an impedance device, or a surge arrester, the grounding is considered to be solid.

False

Which of the following is not permitted to be used to identify a grounded conductor?

Green

Which NEC Table provides grounding electrode conductor (GEC) sizes for communications systems covered in Article 800?

No table required for sizing a communications systems GEC

Requirements for installing AC grounding electrode conductors are provided in ? of Article 250.

Part III

What part of Article 250 covers grounding electrode conductors?

Part III

? of Article 250 specifically applies to grounding systems and circuits over 1,000 volts.

Part X

Permissive requirements in the NEC are characterized by which of the following words or terms?

Shall be permitted

A bonding conductor for a metal water piping system is sized using ? .

Table 250.102(C)(1)

The minimum size required for a supply-side bonding jumper is provided in which of the following NEC tables?

Table 250.102(C)(1)

Which of the following has the responsibility for approval of electrical installations and systems and interpreting NEC rules?

The authority having jurisdiction (AHJ)

Which of the following can be thought of as the foundation of an electrical system?

The grounding electrode system

Article 250 includes provisions that permit guards, isolation, or insulation as alternatives to grounding requirements.

True

Chapters 1 through 7 of the NEC can be modified or amended by the provisions of Chapters 5 through 7

True

Chapters 5, 6, and 7 often modify or amend the general requirements in NEC chapters 1 through 7

True

Exceptions to NEC rules apply only to the rule they follow, unless it is stated differently in the exception.

True

Notes to NEC Tables are mandatory requirements.

True

Notes to NEC tables are enforceable as Code requirements

True

The purpose of the NEC is to provide electrical installation requirements that protect persons and property from electrical hazards arising from the use of electricity.

True

Article 100 of the NEC contains defined terms used in two or more articles, and Section ? of an article often contains defined terms contained only within that article.

XXX.2

Which of the following functions are performed by an equipment grounding conductor (EGC)?

a. Bonding b. Effective ground-fault current path c. Grounding of equipment

A(n) ? is defined as a reliable conductor that ensures continuity and conductivity between metal parts required to be electrically connected.

bonding conductor or jumper

Chapters 1 through 4 of the NEC apply ? .

generally

A grounded conductor of a system could be a ? conductor or a phase conductor.

neutral

NEC Table 250.66 is used for sizing all of the following except ? .

wire-type main bonding jumper(s)

The minimum-size bonding conductor for metal parts associated with neon sign installations shall not be less than ?

14 AWG copper

How many equipment grounding conductors are required to be installed with branch circuits serving patient care spaces?

2

If a service is supplied with 300 kcmil copper ungrounded service conductors, what is the minimum size required for a wire-type supply-side bonding jumper?

2 AWG copper

What is the largest size aluminum grounding electrode conductor required by the NEC?

250 kcmil

Which part of Article 250 applies specifically to grounding DC systems?

VIII


Conjuntos de estudio relacionados

NUR 322 - exam 4 practice questions - ATI, prepU, etc

View Set

Unit 37: Air Distribution and Balance

View Set

Module 26209-20 grounding and bonding

View Set

PSCH 352 Cognition and Memory Ch. 1, 3-7

View Set

HIST2620 Ch 24, HIST2620 Chapter 23, HIST2620 CH 25

View Set

Everfi Financial Literacy Lesson 1 Quiz

View Set

Chapter 14 Basics of Health Insurance

View Set