2014 NEC Wiring and Protection
a clothes closet or bathroom
A panelboard for a residence shall not be installed in ______.
clothes closets
Circuit breakers shall not be located in the vicinity of easily ignitable material such as in _______.
to facilitate overcurrent device operation in case of ground faults
Conductive materials enclosing electrical conductors are grounded to _______.
Where installed within a building in a raceway enclosed by 2" of brick and where installed under not less than 20" of concrete beneath a building.
Conductors shall be considered outside a building ______.
0.06"
Electrodes of nonferrous metal shall be at least ______ in thickness.
attached garage, detached garage with power and basement
For one-family dwelling, at least one receptacle outlet is required in each _______.
115/230
For the purpose of calculating branch-circuit and feeder loads, _______ is NOT a nominal system voltage.
for boat hoist installed indwelling unit locations, for the kitchen dishwasher branch circuit and outdoor in public spaces
GFCI protection is required for personnel ______.
not required to be accessible
The connection of a grounding electrode conductor to a driven ground rod shall be ______.
service-entrance conductors
The de grounding electrode conductor is sized by the rating of the ______.
55amps
The feeder conductor ampacity must not be less than of the service-entrance conductors where the feeder conductors carry the lid supplied by service-entrance conductors with an ampacity of ______ or less.
#10
The frame of an electric range may be grounded by being connected to the grounded conductor of the 120/240v branch circuit, if the grounded conductor is not less than a _______ copper.
8'
The grounding electrode shall be installed such that ______ of length is in contact with the soil.
work areas, storages areas and tool storage area
Unfinished basements are defined as portions or areas of basements not intended as habitable rooms and limited to _______.
100
A #6 fixture wire is considered protected by a 20 amp overcurrent device up to _______ feet.
one and two family dwellings
A 125 volt, 15 or 20 amp receptacle shall be for the servicing of heating, air conditioning and refrigeration equipment in _______.
20'
A bare #4 copper conductor installed near the bottom of a concrete footing that is in direct contact with earth may be used as a grounding electrode conductor when the conductor is at least ______ in length.
#6
A bonding bar near the grounding electrode conductor. The bonding bar shall be connected to the grounding electrode with a minimum _______ copper conductor.
shall be
AC circuits of less than 50 volts ______ grounded if supplied by a transformer whose supply system exceeds 150 volts to ground.
True
AC circuits of less than 50 volts must be grounded if supplied by a transformer whose supply system exceeds 150 volts to ground.
arc-fault circuit-interrupter
An AFCI is an _______.
shall not
An exothermic or irreversible compression connection to fireproofed structural metal ______ be required to be accessible.
ground fault protection for personal and at least one 20 amp branch circuit
Bathroom receptacle outlets shall be by _______.
not be supplied from a dwelling unit's panelboard
Branch circuit in multifamily dwellings for the purpose of alarm, signal, communications, central lighting, or other needs for public or commercial areas shall _______.
ampere
Circuit breakers must be marked with their _______ rating in a manner that will be durable and visible after installation.
will not be burned or otherwise injured by their operation
Circuit breakers shall be so located or shielded so that persons _______.
6
Each electrode of one grounding system shall not be less than ______ feet from any other electrode of another grounding system.
2
Feeders containing a common neutral are permitted to supply _______ sets of 4-wire feeders,
#18
Fixture wire shall be considered as protected by 20 amp branch circuit up to 50' if it is a ______ AWG.
10 ft
For hallways of ______ or more in length at least one receptacle outlet shall be required.
will not
Ground-fault protection that functions to open the service disconnect _______ protect(s) service conductors or the equipment on the line side.
uninsulated, a continuous green, if covered and continuous green with yellow stripe, if covered
Grounding conductors running with circuit conductors may be ______.
25
Grounding of a metal raceway used to protected Romex is required if the raceway is _____ feet or over, or within reach of ground or grounded metal.
isolated and guarded
Handles or levers of circuit breakers, and similar pets which may move suddenly in such a way that persons in the vicinity are likely to be injured by being struck by them, shall be ______.
12
In each kitchen and dinning area a receptacle outlet shall be installed at each counter space _______ inches or wider.
manual override
Lighting outlets can be controlled by occupancy sensors equipped with a _______ that will allow the sensor to function as a wall switch.
below all energized conductors and below all transformers
Locations of lamps for outdoor lighting shall be _______.
readily accessible
Overcurrent device must be _______.
shall not
Overhead service conductors ______ be supported to hardwood trees.
False
Overhead service conductors can be supported to hardwood trees.
only as a replacement item in existing installations
Plug fuses of the Edison-base type shall be used ______.
may be located conveniently for permanent furniture layout
Receptacle installed in a guest room of a motel _______.
shall not
Service conductors supplying a building ______ be permitted to pass through the interior of another building or structure.
orange
The code has assigned the color ______ to the high-leg of a 4-wire delta connected secondary.
limited to storage or storage work areas
The codes defined "unfinished basement" as portions or areas of the basement ______.
gray
The color ______ May have been used in the past as an unguarded conductor. Care should be taken when working on existing systems.
accessible
The connection of a grounding clamp to a electrode shall be _______.
grounded conductor at the service, grounding electrode conductor and service equipment conductor enclosure
The interior metal water piping system shall be bonded to the _______.
12"
The maximum distance that a SE cable strap can be from the meter base or service head is _______.
15
The maximum overcurrent protection for a #14 copper THHN wire installed in a raceway is ______ amperes.
15 amps
The minimum allowed rating for the service disconnect of a single circuit installation is _______.
18
The minimum clearance for service drops, not exceeding 600 volts, over commercial areas subject to truck traffic is ______ feet.
125
The minimum feeder-circuit conductor size, before the application of any adjustment or correction factor, shall have an allowance ampacity equal to or greater than the noncontinuous load plus _______ percent of the continuous load.
#6
The smallest aluminum or copper-clad conductor permitted for service-entrance is _______.
a master handle and handle ties
Two or three single-pole switch or breakers, capable of individual operations, shall be permitted on multiwire circuits, one pole for each ungrounded conductor, as one multipole disconnect provided they are equipped with ______ to disconnect all conductors of the service with no more than six operations of the hand.
#4 AWG
What is the MINIMUM size copper grounding conductor required to serve a multisection motor control center equipped with a 300-amp overcurrent device?
#3/0
What size copper grounding electrode conductor is required for a #1500 kcmil copper service conductor?
outside
When determining the load on the "volt-amps per square foot" basis, the floor area shall be computed from the _______ dimensions of the building.
#10
When outside overhead wiring is used, with no messenger cable, the minimum size cooper wire allowed for spans up to 50 feet is _______.
underground metallic gas pipe
Which of the following may not be used as a grounding electrode?
at least one switch-controlled lighting outlet
Which of the following shall be installed at or near equipment requiring servicing such as HVAC equipment in attic or crawl spaces?
bonding
Which of the following shall be provided where necessary to assure electrical continuity?
15amp
A circuit containing #12 THHN conductors is a ______ rated circuit when protected by a 15amp rated circuit breaker.
grounded
A continuous white or natural gray covering on a conductor shall be used only for the ______ conductor.
receptacle outlet.
A cord connector that is supported by a permanently installed cord pendent shall be considered a ______
25
A feeder tap in a raceway terminating in a single circuit breaker with an ampacity 1/3 of the feeder conductors May extend not over ______ feet.
18
A metal elbow installed underground in a run of nonmetallic conduit is not required to be grounded, it it is isolated by a minimum over of a least _______ inched to any part of the elbow.
Still an acceptable grounding electrode, but it must be supplemented by at least one additional grounding electrode.
A metal underground water pipe, in direct contact with the earth for at least 10 ft, has traditionally been a preferred grounding electrode. For all new construction, a metal underground water pipe is _______.
rod, pipe or plate
A single electrode consisting of a _______ which does not have a resistance to ground of 25 ohms or less shall be augmented by one additional electrode.
25
A single grounding electrode is permitted when the resistance to ground does not exceed ______ ohms.
it is supplemented by one or more additional electrodes
A single made electrode with a resistance to ground of more than 25 ohms is a proved as a grounding electrode system if _______.
False
An exothermic or irreversible compression connection to fireproofed structural metal is required to be accessible.
permitted
An individual 20 amp circuit is ______ to supply power to a single bathroom in a dwelling for receptacle outlet(s) and other equipment with in the same room.
True
An individual 20 amp circuit is permitted to supply power to a single bathroom in a dwelling for receptacle outlet(s) and other equipment within the same room.
at the point where the conductor receives its supply
An overcurrent device shall be located in a circuit _______.
ungrounded conductor
An overcurrent trio of a circuit shall be connected in series with each ______.
6'
Appliance outlets installed for a specific appliance shall be installed within ______ of the intended location of the appliance.
communications, signal and central alarm
Branch circuit in dwelling units shall supply only loads within that dwelling unit or loads associated only with that dwelling unit. Branch circuit required for the purpose of lighting, _______ or other needs for public or common areas shall not be supplied from a dwelling unit panelboard.
threadless couplings and connectors made up tight for rigid metal conduit, IMC and EMT and standard locknuts or bushings
Electrical continuity at service equipment shall be assured by ______.
660 .... 750
Heavy-duty lamp holders shall have a rating not less than _______ watts of the admedium type, and not less than _______ watts of any type.
white
Receptacles, polarized attachment plugs, and cord connectors for plugs and polarized plugs must have the terminal intended for connection to the grounded conductor identified. Indemnification must be by a metal or metal coating that is substantially ______ in color, or by the word white or the letter "W" located adjacent to the identified terminal.
service head
Services cables must be equipped with a _______ listed for use in a wet location.
True
Supplementary overcurrent devices used in luminaries or appliances are not required to be readily accessible.
according to Table 250.102(C)(1)
Supply bonding jumpers must be sized _______.
Kitchen, pantry, breakfast room and dining room
The National Electrical Code requires at least two small appliance branch circuits for dwellings. Either or both of these two circuits shall be permitted to supply circuits in which of the following four rooms?
120 volts
The maximum voltage allowed to supply listed electric-discharge lighting in residences, hotels, motels and similar occupancies is ______.
#10
The minimum size of a copper equipment grounding conductor required for equipment connected to a 40 amp circuits _______.
whether it is in the open or closed position
The service disconnecting means shall plainly indicate______.
service equipment
The terminal bar in a panelboard is connected to the neutral bar only when the panelboard is used as ______.
5 kw
Using the general method of calculation what is the minimum demand for a household clothes dryer?
65
Using the optional method of calculation for a single-dwelling unit, the central space heating would be calculated at ______ percent.
kitchen and bath
Wall-switch controlled receptacles in dwelling units in lieu of lighting outlets are allowed in all habitable rooms except _______.
within the first five feet entering the building
When using the interior metal water piping system for the grounding electrode, the connection of the grounding electrode to the water piping system must be made ______.
3
When wiring a dwellings bathroom you shall install at least one receptacle no less than ______ feet of the outside edge of the basin.
branch-circuit
Where a ______ supplies continuous loads or any combination of continuous and noncontinuous, the rating of the overcurrent device shall not be less than the continuous load plus 125% of the continuous load.
grounded
Where a change occurs in the size of the ungrounded conductor, a similar change may be made in the size of the ______ conductor.
largest
Where a single equipment grounding conductor is run with multiple circuits conductors in the same raceway or cable, it shall be sized for the ______ overcurrent device protecting conductors in the raceway or cable.
white with colored stripes (other than green) or distinguished by other suitable means
Where conductors of different systems are installed in the same raceway, one system shall have a neutral having an outer covering of white or natural gray and each other system having a neutral shall have an outer covering of ______.
the extension cord's listing
Where flexible cord is used in listed extension cord sets, the conductor are considered protected against overcurrent when used within______.
18"
Which using 2 1/2" rigid steel conduit for a through-the-root 120/240 volt service mast, the minimum distance the conduit can protrude above the roof is ______.