Lesson 10: Test Instruments - How to use a Megohmmeter
A cable is considered good if it reads one megohm for each kilovolt of cable rating.
True
During a megohmmeter cable test, leakage current can take two forms: current through the insulation, and current ? . a. along the surface of the insulation b. leakage at the pothead c. leakage into the neutral/ground d. tracking at insulators
a. along the surface of the insulation
When performing a time resistance test on a cable, the megohmmeter test usually runs for ? , depending on the meter manufacturer and the voltage applied. a. 1-9 minutes b. 1-10 minutes c. 5-15 minutes d. 6-20 minutes
b. 1-10 minutes
Insulation resistance opposes ? current either through or over the surface of the insulation when voltage is applied. a. initial b. leakage c. primary d. secondary
b. leakage
A megohmmeter can only be used to test the insulation of cables.
False
A megohmmeter test on a section of faulted underground cable can pinpoint the area of the fault.
False
Megohmmeter tests are extensive; a simple pass/fail test is not available when using a megohmmeter.
False
OSHA 1910.268(o) calls for safe work practices to be in place when doing high-voltage testing.
False
The guard lead from a megohmmeter reads the voltage leakage that might be present when checking a cable.
False
A megohmmeter test is a nondestructive test. This means that a setting of ? should be used on a secondary cable rated up to ? . a. 500 / 600 V b. 600 / 500 V c. 1,000 / 600 V d. 5,000 / 4,000 V
a. 500/ 600V
Most megohmmeters are rated at ? DC or higher. a. 600 V b. 900 V c. 1,000 V d. 10,000 V
c. 1,000V
A megohmmeter uses a high ? voltage to perform an insulation test on a cable. a. AC b. constant/steady/filtered c. DC d. variable
c. DC
When calculating the resistance of a circuit, ? Law applies. a. Kirchhoff's b. Norton's c. Ohm's d. Thevenin's
c. Ohm's
When using a megohmmeter to test a faulted section of cable, before the test is conducted, the cable must be ? . a. cable prepared to specifications b. checked for current c. grounded to drain any capacitance d. sealed from the environment
c. grounded to drain any capacitance
When preparing for a megohmmeter test on a section of underground cable, both ends of the concentric neutral must be ? . a. bonded to the conductor under test b. connected to separate ground rods c. isolated from ground d. tied together
c. isolated from ground
One reason to perform a megohmmeter test would be if there was suspected damage to the insulation by a ? . a. CT drawing current from the cable b. faulty ground c. related component failure d. solid neutral to ground connection
c. related component failure
A megohm is equal to ? . a. 100,000 Ω b. 250,000 Ω c. 500,000 Ω d. 1,000,000 Ω
d. 1,000,000Ω
A factor that can cause insulation to degrade is ? . a. electrical stress b. mechanical stress c. thermal stress d. all of the above
d. all of the above
One of the things maintenance testing of cable indicates is the ? . a. insulation thickness of the cable b. kVA capability of the cable c. presence of water treeing d. remaining life of the cable
d. remaining life of the cable
While performing a megohmmeter cable test, if the meter shows 0, it is probably a ? fault. a. high-resistant b. low-resistant c. series d. shunt
d. shunt