Article 430

Lakukan tugas rumah & ujian kamu dengan baik sekarang menggunakan Quizwiz!

Overcurrent protection for motor control circuits shall not exceed _____ percent if the conductor is based on Table 310. 15(B)(17) and does not extend beyond the motor control equipment enclosure.

400 430.72(B)(2) and Table 430.72(B), Column B, Note 2

A motor controller shall open all conductors to the motor where not used as a disconnecting means.

False

A horsepower-rated _____ having a horsepower rating not less than the motor rating shall be permitted to serve as the disconnecting means.

attachment plug and receptacle flanged surface inlet and cord connector 430.109(F)

A _____ rated in amperes shall be permitted as a controller for all motors.

branch-circuit inverse time circuit breaker and molded case switch

A _____ shall be located in sight from the motor location and the driven machinery location.

disconnecting means

The motor disconnecting means for a motor shall _____ whether it is in the open (off) or closed (on) position.

plainly indicate

A motor can be provided with combined overcurrent protection using a single protective device to provide branch-circuit _____ protection where the rating of the device provides the overload protection specified in 430.32.

short-circuit ground-fault motor overload

The maximum rating or setting of an inverse time breaker used as the motor branch-circuit short-circuit and ground-fault protective device for a single-phase motor is _____ percent of the full-load current given in Table 430.248.

250

Torque requirements for motor control circuit device terminals shall be a minimum of _____ lb-in. (unless otherwise identified) for screw-type pressure terminals used for 14 AWG and smaller copper conductors.

7

For stationary motors of 2 hp or less and 300V or less on ac circuits, the controller can be an ac-rated only general-use snap switch where the motor full-load current rating is not more than _____ percent of the rating of the switch.

80 430.83(C)(2)

Open motors having commutators or collector rings shall be located or protected so that sparks cannot reach adjacent combustible material. This shall not prohibit the installation of these motors _____.

on wooden floors

The motor disconnecting means shall not be required to be in sight from the motor and the driven machinery location, provided _____.

the controller disconnecting means is lockable, in accordance with 110. 25 locating the motor disconnecting means within sight of the motor is impractical locating the motor disconnecting means within sight of the motor introduces additional or increased hazards to people or property

A separate overload device used to protect continuous-duty motors rated more than 1 hp shall be selected to trip at no more than _____ percent of the motor nameplate full-load current rating if marked with a service factor of 1. 15 or greater.

125 430.32(A)(1)

Conductors supplying several motors shall not be sized smaller than _____ percent of the full-load current rating of the highest rated motor, plus the sum of the full-load current ratings of all other motors in the group, plus the ampacity of other loads.

125

A branch-circuit overcurrent device can serve as the disconnecting means for a stationary motor of 1/8 hp or less.

True

A feeder supplying fixed motor load(s) shall have a protective device with a rating or setting _____ branch-circuit short-circuit and ground-fault protective device for any motor in the group, plus the sum of the full-load currents of the other motors of the group.

not greater than the largest rating or setting of the

Motors shall be located so that adequate _____ is provided and so that maintenance, such as lubrication of bearings and replacing of brushes, can be readily accomplished.

Ventilation

Overload devices are intended to protect motors, motor control apparatus, and motor branch-circuit conductors against _____.

excessive heating due to motor overloads excessive heating due to failure to start

A motor disconnecting means can be a listed _____.

molded case circuit breaker motor-circuit switch rated in horsepower molded case switch 430.109(A)(1), (2), and (3)

The disconnecting means for a motor controller shall be designed so that it cannot _____ automatically.

Close

The motor branch-circuit short-circuit and ground-fault protective device shall be capable of carrying the _____ current of the motor.

Starting

In determining the highest rated motor for purposes of complying with 430.24, 430.53(B), and 430.53(C), the highest rated motor shall be based on the rated full-load current as selected _____.

from Tables 430.247, 430.248, 430.249, and 430.250

If a motor disconnecting means is a motor-circuit switch, it shall be rated in _____.

horsepower

Motor controllers and terminals of control circuit devices shall be connected with copper conductors unless identified for use with a different conductor.

True

The disconnecting means for the controller and motor shall open all ungrounded supply conductors.

True

Unless overload protection is provided by other approved means, the minimum number of overload units required for a three-phase alternating-current motor is _____.

Three

.Each motor shall be provided with an individual controller.

True

The motor controller shall have horsepower ratings at the application voltage not _____ the horsepower rating of the motor.

Lower than

Each motor shall be provided with an individual controller.

True

For general motor applications, the motor branch-circuit short-circuit and ground-fault protection device shall be sized based on the _____ values.

NEC Table

A motor controller shall open all conductors to the motor where not used as a disconnecting means. True

False 430.84

Motor control circuit conductors that extend beyond the motor control equipment enclosure shall have short-circuit and ground-fault protection sized not greater than _____ percent of the value specified in Table 310. 15(B)(16) for 60º C conductors.

300

Where more than one motor disconnecting means is provided in the same motor branch circuit, at least one of the disconnecting means shall be readily accessible.

True

Where the motor short-circuit and ground-fault protection devices determined by Table 430.52 do not correspond to the standard sizes or ratings, a higher rating that does not exceed the next higher standard ampere rating shall be permitted.

True

Feeder tap conductors supplying motor circuits, with an ampacity at least one-third that of the feeder, shall not exceed _____ ft. in length.

25 430.28(2)

Motor control circuits shall be arranged so they will be disconnected from all sources of supply when the disconnecting means is in the open position.

True

The motor _____ currents listed in Tables 430.247 through 430.250 shall be used to determine the ampacity of motor circuit conductors and short-circuit and ground-fault protection devices.

full-load


Set pelajaran terkait

Animal Science Final Exam Part 1

View Set

Child Development (Eric Erikson)

View Set

Module 1 assessment practice qs

View Set

Network+ 8th Edition Chapter 12, Network+ 8th Edition Chapter 4, Network+ 8th Edition Chapter 6, Network+ 8th Edition Chapter 5, Network+ 8th Edition Chapter 3, Network+ 8th Edition Chapter 2, Network+ 8th Edition Chapter 1, Network+ 8th Edition Chap...

View Set

chapter 12 managing human resources

View Set

Child Abuse and Neglect: Module 3

View Set