3rd year level 1 lesson 14 transformers- 3 phase connections II

Ace your homework & exams now with Quizwiz!

False

An open wye-open delta transformer bank will operate with a floating or grounded primary neutral bus.

False

Closed transformer banks that deliver 240-volt, 3-phase and 120/240-volt, single-phase power operate with fewer losses than open banks that supply similar loads.

2400 volts

Transformers installed on a 4.16-kilovolt, 4-wire wye system can have primary voltage ratings of 4,160 volts or ? .

False

Transformers with primary windings in a delta configurations can only be connected to delta 3-wire primary circuits.

True

Two delta-wye transformer banks can be paralleled if voltages and angular displacements are the same.

347 V/Y

To provide a 347/600-volt, 3-phase service, transformers with a secondary voltage rating of ? must be ? banked.

277 V

To supply 480-volt, 3-phase power with the transformer secondary coils banked in a wye configuration, the transformer secondary voltage ratings must be ? .

True

The grounded primary neutral of an open wye-open delta transformer bank carries full primary current.

36 A

A closed 150-kVA delta-wye bank is connected to a 2,400-volt, 3-wire line. The three transformers are operating at full load. The current through the primary leads is ? . (Round the FINAL answer to the nearest whole number.)

30 KVA

A closed transformer bank supplies 240-volt, 3-phase and 120/240-volt, single-phase power. With a single-phase load of 30 kVA and a 3-phase load of 60 kVA, the total load on each of the power pots is ? .

60 kva

A closed wye-delta transformer bank supplies 240-volt, 3-phase and 120/240-volt, single-phase power. With a single-phase load of 45 kVA and a 3-phase load of 90 kVA, the total load on the lighter transformer is ? .

24 kva

A closed wye-delta transformer bank supplies 240-volt, 3-phase power and 120/240-volt, single-phase power on a 4-wire service line. If the single-phase load is 36 kVA, the transformer with the grounded X2 bushing will supply ? of that load.

True

A transformer bank provides 240-volt, 3-phase and 120/240-volt, single-phase power. A vector line drawing of the secondary shows the 208-volt wild leg is at the point farthest from the grounded X2 terminal.

43.3 kva

An open transformer bank supplies 3-phase power on a 3-wire service line. The transformers are each rated at 25 kVA. The power rating of this bank is ? .

True

If a CSP transformer is used in a closed wye-delta transformer bank as the lighter, there is a risk of an open neutral condition on the single-phase, 120/240-volt circuit if the secondary circuit breaker is opened or trips.

heads to tails

The secondary vector lines of a wye-delta phasor drawing are connected ? .

True

Transformers with secondary coil ratings of 120/240 volts can supply a 240/416-volt service with the secondary coils connected in series and banked in a wye configuration.

parallel/ wye

Transformers with secondary voltage ratings of 120/240 volts can be used to supply a 120/208-volt load when the secondary coils are connected in ? and ? banked.

34.6 A

Under a balanced load condition, the primary transformer coils of a closed delta bank each draw 20 amperes. The current through each of the primary leads is ? .

240 v

Which one of the following 3-phase service types requires a delta secondary configuration?

False

Wye-delta transformer banks can be connected with either 30° or 120° angular displacements.

86.6 %

An open wye-open delta bank with equally sized transformers has a kVA rating of ? of the combined transformer power ratings.

173 kva

A 100-kVA transformer of a 300-kVA wye-delta bank has failed. Power has been restored by converting the system to open wye-open delta. The power rating of the open bank has been reduced to ? .

271 A

A 225-kVA delta-wye transformer bank feeds a 480-volt secondary circuit. The secondary windings draw 271 amperes at full load. The current through each of the two X terminal to star point conductors is ? .

361 A

A 300-kVA transformer bank with the secondary windings configured in wye feeds a balanced 480-volt load. At full load, or 100% of the power rating, the current through each of the secondary load lines is ? .

90 A

A 75-kVA closed wye-delta transformer bank feeds a 3-wire, 480-volt load. When operating at full rated capacity, the current on each of the three load lines is ? . (Round the FINAL answer to the nearest whole number.)


Related study sets

Quiz 8 Nutrients Essential to Fluid and Electrolyte Balance (Chapter 7)

View Set

Chemical Reactions and Equations

View Set

Chapter 14, Retailing, direct marketing and wholesaling

View Set

Psychology of the Family Chapters 1-4

View Set

Oxford Discover 6 - Unit 11 with Mr. Ahmed Rizk

View Set

Lesson 9 : Intra-AS and Inter-AS Routing

View Set

Cultural Anthropology Makeup Exam Reading Quiz Questions

View Set

Amlit (left out: 3 narcissistic traumas, montage, popular culture, postmodern poetry, postmodern reiteration, realistic domestic drama, )

View Set

Exam 1 MAN 4720 Strategic Management

View Set